Tyco STAR Model A Manual Download Page 11

This procedure is used to verify that the Model A Preaction
Valve will remain set if the electric detection system operates
but the sprinkler system remains in its normally pressurized
condition.

3. Open the Inspector’s Test Connection but be prepared

to close it, as well as the Accelerator Control Valve (Fig.
8), if applicable, immediately after verifying the following:
a. If the system is equipped with an Accelerator, verify

that the time to Accelerator trip is essentially the
same as in previous tests, and verify that the Differ-
ential Chamber Pressure Gauge (Fig. 7) decreases
to a pressure below 20% of the water supply pres-
sure.

b. Verify that the Low Pressure Alarm Switch (Fig. 7)

and its associated alarms operate properly. The
Low Pressure Alarm Switch should operate at the
previously established pressure (refer to Installa-
tion section, Step 7).

Close the Inspector’s Test Connection, and, if applica-
ble, close the Accelerator Control Valve.

4. Close the Differential Chamber Supply Control Valve

(Fig. 7).

5. Close the System Shut-Off Valve (Fig. 1) after the sys-

tem air pressure has been restored to normal.

6. Manually restore the electric fire detection system to a

normal condition in accordance with the manufacturer’s
instructions. The Solenoid Valve will then be de-ener-
gized and returned to its normally closed position.

7. Open the Differential Chamber Supply Control Valve.
8. Open the Main Control Valve (Fig. 1) one turn beyond

the position at which water just begins to flow from the
Main Drain Valve.

9. Close the Main Drain Valve (Fig. 7).

10. Close the Air Supply Control Valve (Fig. 7).
11. Open the Dry Pilot Actuator by partially opening the Trip

Test Flow Valve (Fig. 1) to relieve air pressure at the in-
let to the Actuator. Verify that there is no leakage out the
Dry Pilot Actuator.

NOTES

During this procedure, the Dry Pilot Actuator is opened;
however, the Solenoid Valve should remain closed and the
Model A Preaction Valve Differential Chamber should remain
pressurized.
This procedure is used to verify that the Model A Preaction
Valve will remain set if the Dry Pilot Actuator operates due to
loss of system air pressure and the electric detection system
remains in a normal condition.

12. Open (energize) the Solenoid Valve by operating the re-

leasing panel, and verify the following:
a. Verify that the Model A Preaction Valve operates,

as is indicated by a discharge of water from the Trip
Test Flow Valve and the Automatic Drain Valve. The
Automatic Drain Valve may or may not close de-
pending on the amount of flow past the partially
open Main Control Valve.

b. Verify that the Waterflow Pressure Alarm Switch

(Fig. 7) and its associated alarms properly operate.

c. Verify that the Water Motor Alarm, if applicable,

properly operates.

NOTE

This procedure simulates opening of both the Dry Pilot Ac-
tuator (loss of system air pressure) and Solenoid Valve
(operation of the releasing panel) to verify automatic system
operation.

13. Reset the Model A Preaction Valve in accordance with

the Setting Procedure section.

SERVICE RECOMMENDATIONS

Drop In Water Supply Pressure Below Normal Range

NOTE

If the water supply pressure is significantly reduced be-
low the normally expected static pressure range (as
could occur in the case of a water main break or repair),
and there is a subsequent drop in the differential cham-
ber water pressure below its normal range (due, for exam-
ple, to a leak in a piping connection to or from the differ-
ential chamber or, a leak in the differential chamber
check valve caused by dirt or debris in the check valve
seal area), a preaction valve such as the Model A could
inadvertently trip, if its water supply pressure is quickly re-
stored.
A drop in the water supply pressure to below its normal
range (as in the case of an interrupted water supply condi-
tion) constitutes an emergency impairment as defined by
NFPA 25. Should this condition occur, immediately close
the main control valve 
and utilize the following proce-
dure to reset the system:

1. Prior to the water supply pressure being restored to the

closed main control valve, note the pressure indicated
by the differential chamber pressure gauge and,
whether the pressure is within the normally expected
range.

2. If the differential chamber pressure is below the normal

range, check for and correct any source of leakage from
the differential chamber, prior to resetting the system.

3. After the water supply pressure is restored to the main

control valve, reset the Model A Preaction Valve in ac-
cordance with the Setting Procedure section.

NOTE

For fire protection systems subject to an emergency im-
pairment caused by an interrupted water supply condi-
tion, it is recommended that consideration be given to in-
stalling a low water supply pressure switch, with the
appropriate alarm/indications, to monitor the water supply
pressure.

Leakage From Vent Fitting (23 - Fig. 6); and
Annual Inspection of Differential Valve Disc
(36 - Fig. 2)
The Differential Valve Disc is to be inspected at least an-
nually, or when leakage is present from the Neutral Cham-
ber Vent Fitting.
When removing the Differential Housing Cover to gain ac-
cess to the Differential Valve Disc, first loosen all of the
Differential Housing Bolts, and then replace the top two
Differential Housing Bolts with 6 inch long stud bolts as
shown in Figure 11. The lower two Differential Housing
Bolts and Cover can then be removed while the Differen-
tial Housing remains temporarily supported by the stud
bolts.
Remove the Differential Housing Cover (27 - Fig. 2) and
then remove the Differential Valve Plunger Assembly for
cleaning and inspection. Carefully clean the seating sur-
face on the Differential Valve Seat (30 - Fig. 2), as well as
the counterbore where the Differential Valve Plunger O-
ring (34 - Fig. 2) seats. Carefully clean and inspect the Dif-
ferential Valve Plunger O-ring and Differential Valve Seat.
Do not unnecessarily remove the grease from the Differ-
ential Valve Plunger O-ring. Verify that the O-Ring is lubri-
cated with Grease (41 - Fig. 2). Use only Dow Corning
FS3452 Flurosilicone Grease for lubricating the Differen-
tial Valve Plunger O-ring.
With reference to Figure 2, replace the Differential Valve

STAR SPRINKLER INC.

2-4.1.10

Page 11

OBSOLETE

Summary of Contents for STAR Model A

Page 1: ...alve in a se ries configuration is utilized The double seat design of the Model A Preaction Valve isolates the system air pres sure which holds the Dry Pilot Actuator closed The Sole noid Valve remains closed until it is electrically energized by a releasing panel that is operated by either an electric fire detection device or electric manual pull station As an option for water supplies of 35 psi ...

Page 2: ...ainer 1 5596 21 Retaining Lever 1 5621 22 Water Seat Disc 1 5634 23 Disc Retaining Ring 1 5637 24 Air Seat Disc 1 5827 25 Differential Valve Housing 1 5573 26 Differential Valve Housing Gasket 2 5577 27 Differential Valve Housing Cover 1 5574 28 Differential Valve Housing Cover Bolt 5 8 11UNC x 3 1 2 4 1020 27 29 Roll Pin 2 1893 02 30 Differential Valve Seat 1 NR 31 Differential Valve Plunger 1 55...

Page 3: ...MBLY CLAPPER 04 07 05 ASSEMBLY RESTRICTOR LOCATED VALVE ON BACK OF NEUTRAL CHAMBER VALVE PLUNGER ASSEMBLY DIFFERENTIAL CAUTION LATCH POSITION SECOND LATCH CLAPPER LATCH FIRST POSITION REFER TO SETTING PROCEDURE STEP 8 01 08 PUSH HERE TO UNLATCH CLAPPER 02 LEVER RETAINING ENGAGED CLAPPER ARM 03 WATER SUPPLY PRESSURE DIFFERENTIAL CHAMBER SUPPLY DIFFERENTIAL CHAMBER VENT PORT IDENTIFICATION MAIN DRAI...

Page 4: ... pressure in the Differential Chamber is reduced to approximately one fifth of the water supply pressure Opening of both the Solenoid Valve and Dry Pilot Actua tor or operating the Manual Control Station will release water from the Model A Preaction Valve Differential Cham ber faster than it can be replenished through the 3 32 inch 2 4 mm diameter orifice of the Restrictor Assembly A rapid pressur...

Page 5: ... test or performing a system trip test Installation configuration and clearance dimensions are given in Figure 10 The flanged inlet and outlet connec tions are faced and drilled per ANSI Standard B16 1 un less otherwise specified when ordered In order to readily perform the System Inspection Proce dure described in the Maintenance and Service section it is recommended that a System Shut Off Valve ...

Page 6: ...lve S410 1 1133 1 13 1 2 Ball Valve 1 923001002 NO DESCRIPTION QTY PART 14 1 2 Globe Valve 1 460471004 15 1 2 Swing Check Valve 1 460491004 16 1 2 Y Strainer 1 523531005 17 1 2 Spring Loaded Check Valve 1 923221002 18 3 4 Swing Check Valve with 3 32 Orifice 1 524031005 19 1 1 2 Angle Valve 1 460481008 20 Drip Funnel Support Plug 1 922111005 21 Drip Funnel Support 1 922111003 22 Drip Funnel 1 92343...

Page 7: ...ressure setting After verifying the desired pres sure setting tighten the jam nut 9 Suitable provision must be made for disposal of drain water Drainage water must be directed such that it will not cause damage or result in dangerous conditions 10 All conduit and electrical connections are to be made in accordance with the requirements of the Authority Hav ing Jurisdiction and or the National Elec...

Page 8: ...drain close the Inspector s Test Connection all auxiliary drains in the system piping and the Low Body Drain Valve Leave the Main Drain Valve open 6 Clean out the Strainer 16 Fig 6 in the connection to the Model A Preaction Differential Chamber Reassem ble the Strainer after cleaning 7 Remove the Handhole Cover 4 Fig 2 and then care fully clean the Water Seat Disc Air Seat Disc Seat Ring and Clapp...

Page 9: ... also be replaced 12 Service the air dryer if applicable in accordance with the manufacturer s instructions 13 Open energize the Solenoid Valve Fig 7 by manually operating the releasing panel 14 Open the Differential Chamber Supply Control Valve Fig 7 and allow water to discharge from the Dry Pilot Actuator 15 Close the operating lever of the Manual Control Station Fig 7 Close the hinged cover and...

Page 10: ...l station alarms The Model A Preaction Valve is now set for service MAINTENANCE AND SERVICE The Model A Preaction Valve requires regularly sched uled maintenance and service In addition it is recom mended that the proper operation of the system and con dition of the system in which it is utilized be periodically verified in accordance with the following described inspec tion procedure Any impairme...

Page 11: ...edure section SERVICE RECOMMENDATIONS Drop In Water Supply Pressure Below Normal Range NOTE If the water supply pressure is significantly reduced be low the normally expected static pressure range as could occur in the case of a water main break or repair and there is a subsequent drop in the differential cham ber water pressure below its normal range due for exam ple to a leak in a piping connect...

Page 12: ...ntial Valve Plunger Assembly is accomplished by varying the thread engagement be tween the Plunger Nose and the Plunger Start with an overall assembly length of 4 7 8 inches and then insert the Differential Valve Assembly into the Differential Valve Seat With the Clapper Assembly seated and while pulling the Retaining Lever from left to right push the Differential Valve Plunger Assembly completely...

Reviews: