4/8
Installation Instructions Doc. version 4.0
MZX CIM800
MZX Fire detection system
Avoid smearing sealant over the LED surface.
Using a fine nozzle is recommended.
Address settings
The CIM800 has a default factory set address of
255, this must be set to the loop address of the
device using the 801AP MX Service Tool. The
CIM800 may be programmed with the address
prior to being installed by using the internal pro-
gramming port (see Fig. 4) or after being installed
by using the programming port on the front
cover (see Fig. 6).
Cabling
Cables are to be selected in accordance with
Publication 17A-02-D and the requirements of
the current issue of BS5839. Two pairs of con-
nection terminals (L+ and L-) are provided on the
terminal block. These terminals are used for con-
necting the module onto the addressable circuit.
A maximum of one 1.5mm
2
or one 2.5mm
2
cable may be connected at any one terminal.
Associated equipment
The module fits onto a standard dual-gang MK
box, or an ANC8 ancillary housing.
Fig. 5: Sealed LED
1 – Cover
2 – LED
3 – Sealant
1
2
3
NOTICE
Once the address has been
programmed, take note of the device
location and address number, to
include on site drawings.
Fig. 6: CIM800 Contact Input Module Facia Plate
1 – Address setting port
NOTICE
If only one circuit is used the user circuit
must be terminated with 200/100
ohm resistors in parallel or a single 68
ohm EOL resistor.
MX CONSYS configuration selection –
style C (normally closed)
Mode 3
CIM800
2
5
1