background image

TFP152

Page 3 of 4

Step 3.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

6 Sprinkler Wrench (Figure 2). With 

reference to Figure 1, apply the W-Type 

6 Sprinkler Wrench to the wrench flats. 

Torque sprinklers 7 to 14 ft.-lbs. (9,5 to 

19,0 Nm).

Recessed Pendent Sprinklers

The Series TY-B Recessed Pendent 

Sprinklers must be installed in accor-

dance with the following instructions.

Step A.

 After installing the Style 15 or 

Style 20 Mounting Plate, as applicable, 

over the sprinkler threads and with 

pipe-thread sealant applied to the pipe 

threads, hand-tighten the sprinkler into 

the sprinkler fitting.

Step B.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

7 Recessed Sprinkler Wrench (Figure 

3). With reference to Figure 1, apply the 

W-Type 7 Recessed Sprinkler Wrench 

to the sprinkler wrench flats. Torque 

sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 

Nm).

Step C.

 After the ceiling is installed or 

the finish coat is applied, slide on the 

Style 15 or Style 20 Closure over the 

Series TY-B Sprinkler and push the 

Closure over the Mounting Plate until 

its flange contacts the ceiling.

Care and 

Maintenance

The TYCO Series TY-B, 5.6 K-factor, 

Upright (TY315) and Pendent (TY325) 

Sprinklers must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Absence of the outer piece of an 

escutcheon, which is used to cover 

a clearance hole, can delay sprinkler 

operation in a fire situation.
The owner must assure that the 

sprinklers are not used for hanging 

any objects and that the sprinklers are 

only cleaned by means of gently dust-

ing with a feather duster; otherwise, 

non-operation in the event of a fire or 

inadvertent operation may result.
Sprinklers which are found to be leak-

ing or exhibiting visible signs of corro-

sion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or otherwise 

altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned by 

wiping the sprinkler with a cloth or by 

brushing it with a soft bristle brush.
Care must be exercised to avoid dam-

age to the sprinklers - before, during, 

and after installation. Sprinklers dam-

aged by dropping, striking, wrench 

twist/slippage, or the like, must be 

replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. (Ref. Installation 

Section.)
Thereafter, annual inspections per 

NFPA 25 are required; however, instead 

of inspecting from the floor level, a 

random sampling of close-up visual 

inspections should be made.

The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion (e.g., NFPA 25), in addition to the 

standards of any other authorities hav-

ing jurisdiction. Contact the installing 

contractor or sprinkler manufacturer 

regarding any questions.
Automatic sprinklers are recommended 

to be inspected, tested, and maintained 

by a qualified Inspection Service in 

accordance with local requirements 

and/or national codes.

MOUNTING

PLATE

MOUNTING

SURFACE

SERIES

TY-B

2-7/8" DIA.

(73,0 mm)

FACE OF

SPRINKLER

FITTING

2-1/4" DIA.

(57,2 mm)

1/8"

(3,2 mm)

CLOSURE

3/8±5/16"

(9,5±7,9 mm)

1-3/8" (34,9 mm)

5/8" (15,9 mm)

3/4" (19,1 mm)

FLUSH

MOUNTING

SURFACE

SERIES

TY-B

CLOSURE

MOUNTING

PLATE

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

FACE OF

SPRINKLER

FITTING

1/8"

(3,2 mm)

5/16±1/4"

(7,9±6,4 mm)

1/2" (12,7 mm)

1-3/8" (34,9 mm)

FLUSH

7/8" (22,2 mm)

FIGURE 4 

SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325) 

WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 

RECESSED ESCUTCHEON

FIGURE 5 

SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325) 

WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 

RECESSED ESCUTCHEON