TFP152

Page 2 of 4

Operation

The glass bulb contains a fluid which 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and water to flow.

Design 

Criteria

The TYCO Series TY-B, 5.6 K-factor, 

Upright (TY315) and Pendent (TY325) 

Sprinklers are intended for fire protec-

tion systems designed in accordance 

with the standard installation rules 

recognized by the applicable Listing 

or Approval agency (e.g., UL Listing 

is based on the requirements of NFPA 

13, and FM Approval is based on the 

requirements of the FM Loss Preven-

tion Data Sheets). Only the Style 15 

or Style 20 Recessed Escutcheon, as 

applicable, is to be used for recessed 

pendent installations.

Installation

The TYCO Series TY-B, 5.6 K-factor, 

Upright (TY315) and Pendent (TY325) 

Sprinklers must be installed in accor-

dance with this section.

General Instructions

Do not install any bulb type sprinkler if 

the bulb is cracked or there is a loss of 

liquid from the bulb. With the sprinkler 

held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 inch 

(1,6 mm) for the 135°F (57°C) to 3/32 

inch (2,4 mm) for the 360°F (182°C)

temperature ratings.
A leak-tight 1/2 inch NPT sprinkler 

joint should be obtained by applying a 

minimum-to-maximum torque of 7 to 14 

ft.-lbs. (9,5 to 19,0 Nm). Higher levels 

of torque may distort the sprinkler inlet 

and cause leakage or impairment of the 

sprinkler.
Do not attempt to compensate for 

insufficient adjustment in the escutch-

eon plate by under- or over-tightening 

the sprinkler. Readjust the position of 

the sprinkler fitting to suit.

Upright and Pendent Sprinklers

The Series TY-B Upright and Pendent 

Sprinklers must be installed in accor-

dance with the following instructions.

Step 1.

 Install pendent sprinklers in 

the pendent position; install upright 

sprinklers in the upright position.

Step 2.

 With pipe-thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Components:

1/2" NPT

1

5

2

3

4

2"

(50,8 mm)

Frame

Button

Sealing

Assembly

*

6

2 -

-

3

-

1

*

-

6

Deflector

Compression

Screw

-

5

4 - Bulb

2-7/8" (73,0 mm) DIA.

1-3/8"

(34,9 mm)

2"

(50,8 mm)

WRENCH

FLATS

7/16"

(11,1 mm)

NOMINAL

MAKE-IN

STYLE 15 or 20

RECESSED

ESCUTCHEON

7/16" (11,1 mm)

NOMINAL MAKE-IN

Pipe thread connections per ISO 7-1

can be provided on special request.

**

DEFLECTOR

*

Temperature rating is

indicated on Deflector.

DEFLECTOR

*

*

ESCUTCHEON PLATE

SEATING SURFACE

**

**

1/2"

NPT

UPRIGHT

CROSS SECTION

PENDENT

RECESSED PENDENT

WRENCH RECESS

(USE ONLY

END "A")

WRENCH

RECESS

PUSH WRENCH

IN TO ENSURE
ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

FIGURE 1 

SERIES TY-B UPRIGHT (TY315) AND PENDENT (TY325) SPRINKLERS 

5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE

FIGURE 3 

W-TYPE 7 RECESSED 

SPRINKLER WRENCH

FIGURE 2 

W-TYPE 6 

SPRINKLER WRENCH