Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 4
FEBRUARY 2014
TFP152
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers described in this data sheet
are standard response, standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories,
refineries, and chemical plants.
The recessed version of the Series
TY-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
•
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
•
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-B Sprinklers are described in
Technical Data Sheet TFP352. Sprinkler
guards and shields are described in
Technical Data Sheet TFP780.
NOTICE
The Series TY-B Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion, in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Numbers (SINs)
TY315 . . . . . . Upright 5.6K, 1/2˝ NPT
TY325 . . . . . Pendent 5.6K, 1/2˝ NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and VdS Approved
CE Certified
Sprinklers with Polyester Finish are
UL and C-UL Listed as Corrosion-
Resistant Sprinklers.
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi
(17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
360°F (182°C)
†
† UL, C-UL, and VdS Approved only
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . Bronze
Button. . . . . . . . . . . . . . Brass/Copper
Sealing Assembly
. . . . . . . . . Stainless
Steel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . .Glass
Compression Screw. . . . . . . . Bronze
Deflector. . . . . . . . . . . . . . . . . Bronze