Series TY-B, 5.6 K-factor 

Upright, Pendent, and Recessed Pendent Sprinklers 

Standard Response, Standard Coverage

Page 1 of 4 

FEBRUARY 2014 

TFP152

IMPORTANT

Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cau-

tions with respect to handling and 

installation of sprinkler systems and 

components. Improper handling and 

installation can permanently dam-

age a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Series TY-B, 5.6 K-factor, 

Upright (TY315) and Pendent (TY325) 

Sprinklers described in this data sheet 

are standard response, standard cover-

age, decorative 5 mm glass bulb type 

spray sprinklers designed for use in 

light, ordinary, or extra hazard, com-

mercial occupancies such as banks, 

hotels, shopping malls, factories, 

refineries, and chemical plants.
The recessed version of the Series 

TY-B Pendent Sprinkler, where appli-

cable, is intended for use in areas with a 

finished ceiling. This recessed pendent 

sprinkler uses one of the following:

• 

A two-piece Style 15 Recessed 

Escutcheon with recessed adjust-

ment up to 5/8 inch (15,9 mm) from 

the flush pendent position.

• 

A two-piece Style 20 Recessed 

Escutcheon with recessed adjust-

ment up to 1/2 inch (12,7 mm) from 

the flush pendent position.

The adjustment provided by the 

Recessed Escutcheon reduces the 

accuracy to which the fixed pipe drops 

to the sprinklers must be cut.
Intermediate level versions of Series 

TY-B Sprinklers are described in 

Technical Data Sheet TFP352. Sprinkler 

guards and shields are described in 

Technical Data Sheet TFP780.

NOTICE

The Series TY-B Sprinklers described 

herein must be installed and maintained 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion, in addition to the standards of any 

other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition. 

The installing contractor or sprinkler 

manufacturer should be contacted with 

any questions.

Sprinkler 

Identification 

Numbers (SINs)

TY315   . . . . . . Upright 5.6K, 1/2˝ NPT

TY325   . . . . . Pendent 5.6K, 1/2˝ NPT

Technical 

Data

Approvals

UL and C-UL Listed 

FM, LPCB, and VdS Approved 

CE Certified
Sprinklers with Polyester Finish are 

UL and C-UL Listed as Corrosion-

Resistant Sprinklers.

Maximum Working Pressure

175 psi (12.1 bar) 

250 psi (17.2 bar)*

* The maximum working pressure of 250 psi 

(17.2 bar) only applies to the listing by Un-

derwriters Laboratories, Inc. (UL).

Discharge Coefficient

K = 5.6 GPM/psi

1/2

 (80,6 LPM/bar

1/2

)

Temperature Ratings

135°F (57°C) 

155°F (68°C) 

175°F (79°C) 

200°F (93°C) 

286°F (141°C) 

360°F (182°C)

 

† UL, C-UL, and VdS Approved only

Finishes

Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated, 

Chrome Plated, or Brass Plated

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . Bronze

Button. . . . . . . . . . . . . . Brass/Copper

Sealing Assembly

. . . . . . . . . Stainless 

Steel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . .Glass

Compression Screw. . . . . . . .  Bronze

Deflector. . . . . . . . . . . . . . . . . Bronze