Technical
Data

Approvals
UL and C-UL Listed. (Approvals only
apply to the service conditions indi-
cated in the Design Criteria section.)

Maximum Working Pressure
175 psi (12,1 bar)

Pipe Thread Connection
3/4 inch NPT

Discharge Coefficient
K = 16.8 GPM/psi

1/2

(241,9 LPM/bar

1/2

)

Temperature Ratings
160°F/71°C or 212°F/100°C

Finish
Natural Brass, White, or Chrome
Plated

Physical Characteristics
Frame . . . . . . . . . . . . . . Brass
Deflector . . . . . Phosphor Bronze
Compression Screw . . . . . . . . .

. . . . . . . . . . . . Stainless Steel

Hook . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . . Monel
Link Assembly . . . . Solder, Nickel
Button . . . . . . . . . . . . . . Brass
Sealing Assembly . . . . . . . . . .

. . . . . Beryllium Nickel w/Teflon

Patents
Patent Pending

Operation

The fusible link assembly is comprised
of two link halves that are joined to-
gether by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate allowing the sprinkler to acti-
vate and flow water.

Design
Criteria

The Tyco

®

Model EC-17 Extended

Coverage Pendent Sprinklers (SIN
TY7228) are UL and C-UL Listed,

with

the exception of using plastic pallets
as described in 5.6.2.6 of NFPA 13-
2007, for installation in accordance
with the extended coverage pendent
spray sprinkler requirements of NFPA
13, or other applicable NFPA stand-
ards, when used in conjunction with
the following guidelines :

Suitable for the protection of extra
hazard and high-piled storage occu-
pancies where area/density design
criterion are provided.

Suitable for “unobstructed” or “non-
combustible obstructed” construc-
tion.

The Model EC-17 Sprinklers, having
been specifically tested and listed
for noncombustible obstructed con-
struction, are suitable for use within
trusses or bar joists having non-
combustible web members greater
than 1 inch (25,4 mm) when applying
the four times obstruction criteria
rule defined under “Obstructions to
Sprinkler Discharge Pattern Devel-
opment”.

The maximum area of coverage per
sprinkler is 196 sq. ft. (18,2 m

2

).

The maximum distance between
sprinklers is 15 feet (4,6 m) when the
coverage does not exceed 144 ft.

2

(13,4 m

2

), and the maximum dis-

tance between sprinklers is 14 feet
(4,3 m) when the coverage does not
exceed 196 ft

2

(18,2 m

2

).

The minimum distance between
sprinklers is 8 feet (2,44 m).

The minimum flow requirement is to
be based on the design density ap-
plied over the actual area of cover-
age per sprinkler.

For example: when sprinkler spac-
ing is 14 feet by 12 feet - 6 inches
(4,3 x 3,8 m) or 175 ft

2

(16,3 m

2

), and

the design density is 0.3 gpm/ft

2

(16,3 mm/m), the sprinkler design
flow rate is 53 GPM (200 LPM) and
the required design pressure is 10
psi (0,7 bar).

The minimum clearance between
the deflector and the top of storage
is 36 inches (0,9 m).

The ordinary and intermediate tem-
perature rated EC-17 Sprinklers
have been investigated for use in
high-piled storage occupancies at
the hydraulic demand normally as-
sociated with high temperature
sprinklers. As such, the EC-17 sprin-
klers are listed storage sprinklers
having a K-factor greater than 11.2
and having ordinary and intermedi-
ate temperature ratings (i.e., 160F
and 212F). Consequently, the EC-
17 Sprinklers, in accordance with
the NFPA 13, may be used in con-
junction with the density curves for
high temperature sprinklers.

Page 2 of 4

TFP215

FIGURE 1, MODEL EC-17 EXTENDED COVERAGE PENDENT SPRINKLER

6

*

2-3/4"

2"

WRENCH

FLATS

SEATING SURFACE

ESCUTCHEON PLATE

NPT

3/4"

1

2

3

4

5

-

2

Button

Temperature

Deflector

Compression
Screw

Link

Sealing

-

8

*

-

4

7 -

3 -

*

Components:

Frame

1 -

1/2" (12,7 mm)

NOMINAL MAKE-IN

rating is indicated

7

8

(69,9 mm)

(50,8 mm)

Hook

Stem

-

6

5 -

on deflector.

Assembly

Assembly

PENDENT

CROSS SECTION

RECESSED PENDENT

2-7/8" (73,0 mm) DIA.

STYLE 30

ESCUTCHEON

RECESSED

OBSOLETE