Installation

NOTES

Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only and by using the appropriate
sprinkler wrench. Do not grip or apply
any force to the Fusible Link Assem-
bly. Damaged sprinklers must be re-
placed immediately.

A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.

The Model EC-17 Pendent Sprin-
klers 
must be installed in accordance
with the following instructions:

Step 1. The EC-17 Sprinkler must be
installed in the pendent position.

Step 2. With pipe thread sealant ap-
plied, hand tighten the sprinkler into
the sprinkler fitting. Do not apply any
force to the Link Assembly, and handle
the EC-17 Sprinkler only by the Frame
arms.

Step 3. Wrench tighten the EC-17
Sprinkler using only the W-Type 3
Sprinkler Wrench (Ref. Figure 3) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.

The Model EC-17 Recessed Pendent
Sprinklers 
must be installed in ac-
cordance with the following instruc-
tions.

Step A. After installing the Style 30
Mounting Plate over the sprinkler
threads, and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.

Step B. Wrench tighten the EC-17
Sprinkler using only the W-Type 24
Sprinkler Wrench (Ref. Figure 4) and
fully engaging (seating) the wrench on
the sprinkler wrench flats.

Step C. After the ceiling has been in-
stalled, slide the Style 30 Closure over
the Model EC-17 Sprinkler and push
the Closure over the Mounting Plate
until its flange comes in contact with
the ceiling.

Care and
Maintenance

The Tyco

®

Model EC-17 must be

maintained and serviced in accord-
ance with the following instructions:

NOTE

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
replaced.

Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.

Automatic sprinkler systems should be

inspected, tested, and maintained by a
qualified Inspection Service in accord-
ance with local requirements and/or
national code.

TFP215

Page 3 of 4

FIGURE 3

W-TYPE 3

SPRINKLER WRENCH

"FITTING SIDE"

FITTING

TOWARDS SPRINKLER

RECESS

WRENCH

(END "B")

1/4" (6,4 mm)

1/2" (12,7 mm)

MOUNTING

SURFACE

SPRINKLER

FITTING

FACE OF

(12,7±3,2 mm)

1/2±1/8"

(57,2 mm)

2-1/4" DIA.

2-7/8" DIA.

(73,0 mm)

CLOSURE

1-1/2" (38,1 mm)

1-1/4" (31,8 mm)

MOUNTING

PLATE

(3,2 mm)

1/8"

FIGURE 2

MODEL EC-17 RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT

STYLE 30 RECESSED ESCUTCHEON