background image

TFP802

Page 3 of 6

Care and 

Maintenance

The TYCO

 

Type D3 PROTECTOSPRAY 

Nozzles must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection sys-

tem main control valve for mainte-

nance work on the fire protection sys-

tem that it controls, permission to shut 

down the affected fire protection sys-

tem must be obtained from the prop-

er authorities and all personnel who 

may be affected by this action must 

be notified.
Type D3 PROTECTOSPRAY Nozzles 

must never be painted, plated, coated 

or altered in any way after leaving the 

factory; otherwise, the spray perfor-

mance may be impaired.
Care must be exercised to avoid dam-

age to the nozzles before, during, and 

after installation. Nozzles damaged by 

dropping, striking, wrench twist/slip-

page, or the like, must be replaced.
Frequent visual inspections are rec-

ommended to be initially performed 

for nozzles installed in potentially cor-

rosive atmospheres to verify the in-

tegrity of the materials of construction 

and finish as they may be affected by 

the corrosive conditions present for a 

given installation. Thereafter, annual 

inspections per NFPA 25 are required.
Water spray fixed systems for fire 

protection service require regularly 

scheduled care and maintenance by 

trained personnel. In addition to in-

specting nozzles for proper spray per-

formance during water flow trip tests 

of the system, it is recommended 

that nozzles be periodically inspected 

for broken or missing parts (includ-

ing blow-off plugs where applicable), 

loading/obstructions, or other evi-

dence of impaired protection. The in-

spections should be scheduled weekly 

or as frequently as may be necessary, 

and corrective action must be taken 

to ensure that the nozzles will per-

form as intended in the event of a fire.
For installations subject to freezing 

and where blow-off plugs have been 

installed, a periodic inspection must 

be performed for evidence of ice 

build-up from trapped condensate 

which could affect the proper release 

of the blow-off plugs.
The owner is responsible for the in-

spection, testing, and maintenance of 

their fire protection system and devic-

es in compliance with this document, 

as well as with the applicable stan-

dards of the National Fire Protection 

Association (e.g., NFPA 25), in addition 

to the standards of any other authori-

ties having jurisdiction. The installing 

contractor or sprinkler manufacturer 

should be contacted relative to any 

questions.
Water spray fixed systems are recom-

mended to be inspected, tested, and 

maintained by a qualified Inspection 

Service in accordance with local re-

quirements and/or national codes.

80°

65°

140°

95°

110°

125°

160°

180°

0,5

0

1,0

1,5

2,0

2,5

3,0

3,5

4,0

4,5

0

0,5 1,0 1,5 2,0 2,5

NOZZLE CENTERLINE, METERS

RADIAL DISTANCE FROM

AXIAL DIST

ANCE FROM NOZZLE, METERS

95°

65°

80°

110°

125°

140°

160°

180°

0

16

14

12

10

8

6

4

2

0

2

4

6

8

RADIAL DISTANCE FROM

NOZZLE CENTERLINE, FEET

AXIAL DIST

ANCE FROM NOZZLE, FEET

AXIAL DISTANCE

NOZZLE

PLANE OF

PROTECTION

PROFILE

SPRAY

(ORIENTATION)

FIXED ANGLE

GRAVITY

maximum Axial Distances shown in Tables C and D.

The shapes of the Design Spray Profiles remain essentially unchanged over the

Refer to the authority having jurisdiction for their minimum required residual pressures.

3.

psi (1,4 to 4,1 bar). For pressures up to 175 psi (12,1 bar) consult Tyco Fire Protection

Products Technical Services.

Design data applies to a residual (flowing) pressure range at the nozzle inlet of 20 to 60

Design data obtained from tests in still air.

2.

1.

NOTES:

DISTANCE

RADIAL

140°, the Design Spray Profile is the same as the nominal spray angle.

For axial distances of 2 feet (0,6 meters) and less and for nozzle spray angles of 65° to

4.

protection.

The maximum Axial Distances shown in Tables C and D are based on exposure

5.

 FIGURE 2 

WATER DISTRIBUTION DESIGN DATA

Reviews: