background image

TFP802

Page 2 of 6

Design 

Criteria

Nozzle Placement.

 Where direct im-

pingement of water spray onto all of 

the protected surface is required by 

the authority having jurisdiction, the 

nozzles are to be spaced and directed 

so that their spray patterns will com-

pletely cover the plane-of-protection 

with the minimum required average 

density; however, it is recommend-

ed that indoor nozzle spacing be 12 

feet (3,7 m) or less and that outdoor 

nozzle spacing be 10 feet (3,0 m) or 

less. Where rundown or slippage is 

planned, such as, exposure protec-

tion of vessels per NFPA 15, the above 

rec 

ommended indoor and outdoor 

spac ings also apply.
When used for protecting the surfaces 

of a vessel, for example, the nozzles 

are positioned normal to and approxi-

mately 2 feet (0,6 m) from the surface. 

This approach, in conjunction with 

a properly selected spray angle, will 

tend to make more effective use of the 

spray as well as help minimize the dis-

turbance effects of wind/draft condi-

tions on the water spray patterns.

Spray Patterns.

 The Design Spray 

Profiles for the nozzle spray angles of 

65 to 180 degrees are shown in Fig-

ure 2 and apply to discharge pres-

sures of 20 to 60 psi (1,4 to 4,1 bar). 

Discharge pressures in excess of 60 

psi (4,1 bar) will result in a decrease 

in coverage area since the spray pat-

terns tend to draw inwards at higher 

pressures. Refer inquiries on higher 

discharge pressures to the Technical 

Services Department. The maximum 

axial distances between the nozzle tip 

and plane-of-protection, for exposure 

protection, are given in Table C and D. 

When the axial distance from the noz-

zle tip to the plane-of-protection is 2 

feet (0,6 m) or less, the Design Spray 

Profile is the same as the nominal 

spray angles of 65 thru 140 degrees.

Main Pipeline Strainers.

 Main pipe-

line strainers per NFPA 15 are required 

for systems utilizing nozzles with a 

flow path less than 3/8 inch (9,5 mm) 

diameter, i.e., No. 16 thru No. 24 (Ref. 

Table A), and for any system where the 

water is likely to contain obstructive 

material.

Installation

The TYCO Type D3 Protectospray 

Nozzles must be installed in accor-

dance with this section.

General Instructions

A leak-tight 1/2 inch NPT nozzle joint 

should be obtained by applying a min-

imum to maximum torque of 7 to 14 ft. 

lbs. (9,5 to 19,0 Nm). Higher levels of 

torque may cause impairment of the 

nozzle.

Step 1.

 With pipe-thread sealant ap-

plied to the pipe threads, hand tighten 

the nozzle into the nozzle fitting.

Step 2.

 Tighten the nozzle into the 

nozzle fitting using only the W-Type 11 

Sprinkler Wrench (Figure 3). With ref-

erence to Figure 1, apply the W-Type 

11 Sprinkler Wrench to the wrenching 

area.

65°

80°

95°

110°

125°

140°

160°

180°

ORIFICE 

SIZE

MINIMUM  

DIAMETER

K-FACTOR

GPM/psi

1/2

LPM/bar

1/2

NO. 16

0.203”     (5,16 mm)

1.2

17,3

NO. 18

0.250”     (6,35 mm)

1.8

25,9

NO. 21

0.281”     (7,14 mm)

2.3

33,1

NO. 24

0.328”     (8,33 mm)

3.0

43,2

NO. 28

0.375”     (9,53 mm)

4.1

59,0

NO. 32

0.438”   (11,13 mm)

5.6

80,6

NO. 34

0.500”   (12,70 mm)

7.2

103,7

AREA

WRENCHING

2-1/2"

(63,5 mm)

(44,5 mm)

1-3/4"

2-1/16"

(52,4 mm)

1/2" NPT

PIN

DEFLECTOR

SPLITTER

FRAME

NOMINAL MAKE-IN

7/16" (11,1 mm)

ORIFICE SIZE

STAMPED ON

WRENCHING

AREA

DEFLECTOR

STAMPED ON

(INCLUDED ANGLE

SPRAY ANGLE

OF DISCHARGE)

 FIGURE 3 

W-TYPE 11 

SPRINKLER WRENCH

TABLE B 

SELECTION OF SPRAY ANGLES

TABLE A 

SELECTION OF ORIFICE SIZES

 FIGURE 1 

TYPE D3 PROTECTOSPRAY NOZZLES 

NOMINAL DIMENSIONS

Reviews: