Always perform the signal survey with the antenna that will be used on the repeater when it is
installed.
It is recommended to not connect any other equipment such as horns or communicators to
the CP-3500D until the unit is programmed. There is a 6 position dip switch marked SW2 located on
the receiver card. Verify that all of the switches except #3 are in the on position. Any other settings of
this switch will result in improper operation of the CP-3500D panel. Now apply A/C power and
connect charged batteries as shown in figure 4. A short beep may be heard from the receiver piezo
sounder. This is normal. The LCD will show the CWSI logo and will begin to boot up. When the CP-
3500D has finished the boot up process the System Initialization screen will be shown on the LCD.
Note: If there is a communication problem between the receiver pc board and the CP-3500D
main board the LCD will not display the initialization screen. Instead a message that the
receiver board was not found will be shown. If this message appears, power down the CP-
3500D and check the settings of SW2 on the repeater board and proper connection of the
wiring harness between the receiver and CP-3500D main pc board. Reapply power and if the
receiver notice is displayed again, the unit must be returned to the factory.
While the
initialization screen is displayed the system will attempt to communicate with any enrolled devices,
annunciators and repeaters that are in the CP-3500D memory. The CP-3500D will also verify and or
update any relay programming for the repeaters according to the current CP-3500D programming
memory. An estimated time is shown to complete the system initialization. The time shown is
approximate and will vary based on the amount of devices and relays to be found and verified. The
initialization process could take an hour on a system with many devices and programmed relays.
Keep in mind that the CP-3500D system initialization only occurs once when the panel is powered up.
The process cannot be aborted and must be completed prior to letting the user continue with further
programming and system operation. There are two sets of numbers displayed on the screen. Each
set is divided by a /. One set appears under the Devices Checked in header and the other under the
Relays Programmed header. The number to the right indicates a count of the devices and relays
currently in the CP-3500D memory. The number on the left will increment as devices and relays are
found and programmed. The initialization process will end when either the CP-3500D finds all of the
devices and programs all of the relays in memory or the estimated time is exceeded without finding all
of the devices and or programming all of the relays. Any unfound devices when the initialization
process is complete will be shown as a test failure trouble. The receiver board in the CP-3500D
counts as a repeater therefore the number shown for the devices in the system memory will always
show at least 0001 even if no devices or repeaters have been enrolled.
After the system initialization is completed the System Requires Configuration screen will be shown.
Refer to the system programming section of this manual to complete the initial configuration.