2.3 UL Restricted Programming Options
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program feature or
option
Permitted in UL
864? (Y/N)
Possible settings
Settings permitted in UL
864
Aux. output activation
Y
Alarm priority A, B, C, D
Alarm Priority A
Aux. output
deactivation
Y
Reset, Signal Silence
Reset
Relay Box relay
deactivation
Y
Reset, Signal Silence,
Detector Sounder
Silence, Strobe Reset
Reset