background image

2

6-96

Optima™, Omega™ & Glass Bulb Residential Sprinkler

Design and Installation Guide

calculated at 16' x 16'.  Compliance with the single head
flow as well as multiple head flow for the appropriate
spacing must be verified.  The number of sprinklers to
calculate must be verified with the appropriate NFPA
Standard as well as the 

Authority Having Jurisdiction.

More sprinklers may need to be calculated than the
minimum NFPA Standards where unusual conditions
would result in more sprinklers operating.  These
conditions include sloped or beamed ceilings.

V.  Approvals

Central Residential Sprinklers are Listed by Underwriters
Laboratories, Inc. and have passed fire tests designed to
represent fire conditions for the areas listed.  Refer to
Underwriter’s Laboratories, Inc. Publication UL 1626,
“Residential Sprinklers for Fire Protection Service”, for
Residential Sprinkler performance and spray pattern
standards.  For Listed areas of coverage, flows and
pressures use the individual data sheets and this guide.

VI.  Installation

Central Residential Sprinklers must be installed according
to current NFPA 13, NFPA 13D and NFPA 13R Standards
for residential sprinklers.  The 

Authority Having

Jurisdiction, Central's Residential Installation Guide and
the individual data sheets which contain specific criteria on
each sprinkler should be referenced in every installation.

Prior to installation, check for the proper model, style,
orifice size, and temperature rating.  Install sprinklers after
the piping is in place to avoid mechanical damage; replace
any damaged sprinklers.  Avoid installing sprinklers prior to
the use of space heaters for drying of texturing or painting
where expected ambient temperatures exceed 100

°

F/

38

°

C.

Final acceptance of the installation of residential sprinklers
is the responsibility of the 

Authority Having Jurisdiction.

Installation Sequence

Step 1.  The sprinkler must be installed in the pendent
position for pendent sprinklers, and in the sidewall position
for sidewall sprinklers.

Step 2.  Use only a non-hardening pipe joint compound or
Teflon tape.  Apply only to the male threads.

Step 3.  Hand tighten the sprinkler into the fitting.  Use the
appropriate Central Sprinkler Wrench to tighten the unit
into the fitting.  A leak tight joint requires the application of
only 7 to 14 ft.-lbs. of torque.  A  tangential force of 14 to
28 lbs. delivered through a 6" handle will deliver adequate
torque.  Torque levels over 21 ft.-lbs. may distort the orifice
seal, resulting in leakage.

Do not use the push-on escutcheon plate (when
applicable) to hold the unit in position.  The sprinkler will
function properly only when the system piping is anchored
to the building structure.  Otherwise, reaction forces from
system initiation could alter the sprinkler alignment and
disrupt the distribution pattern.   Do not over or under
tighten the sprinkler to compensate for inaccurate
escutcheon plate adjustment.  Re-adjust the sprinkler
fitting as required.

CAUTION

NEVER INTRODUCE WATERGLASS OR
OTHER LEAK STOPPING ADDITIVES TO
ANY FIRE SPRINKLER SYSTEM.

When using Residential Sprinklers, special care must be
taken when installing a CPVC system.  Sprinklers must be
installed after the CPVC manufacturer's recommended
setting time for the primer and cement to ensure that
neither accumulate within the sprinkler.  Other CPVC
specific requirements can be found in the CPVC
Installation Guide.  For example, specific kinds of pipe
dope are not allowed.

When using Residential Sprinklers, special care must be
taken when installing a copper system.  Sprinklers must be
installed only after the inside of the sprinkler drop and
associated fittings have been wire brushed to remove any
residual flux.  Residual flux can cause corrosion and in
extreme cases can impair proper sprinkler operation.

Residential fire sprinkler systems must only be designed
and installed by those competent and completely familiar
with automatic sprinkler system design, installation proce-
dures and techniques.

VII.  Maintenance

Residential Sprinklers must be installed and maintained in
accordance with current NFPA Standards and the
Authority Having Jurisdiction.

4-96

OBSOLETE

Summary of Contents for CENTRAL Omega

Page 1: ...ated more than 3 0 measured vertically from any peaked ceiling C Cold Solder The minimum distance between Residential Sprinklers per NFPA 13D is 8 0 This requirement is based on smooth flat ceiling co...

Page 2: ...on for sidewall sprinklers Step 2 Use only a non hardening pipe joint compound or Teflon tape Apply only to the male threads Step 3 Hand tighten the sprinkler into the fitting Use the appropriate Cent...

Page 3: ...14 or less 7 or less 14 10 6 11 6 5 Pendent 16 8 16 13 8 12 7 8 18 9 19 19 5 14 10 6 GBR 7 16 4 3 14 or less 7 or less 14 10 6 11 6 5 Recessed Pendent 16 8 16 13 8 12 7 8 18 9 19 19 5 16 13 8 GBR 7 16...

Page 4: ...7 34 31 29 27 25 23 22 21 19 18 18 17 5 79 68 59 51 45 40 36 32 29 27 24 23 21 20 18 17 16 16 15 14 4 76 63 63 45 39 34 30 27 24 22 20 18 17 16 15 14 13 13 12 11 3 72 56 45 37 31 27 23 21 18 17 15 14...

Page 5: ...ated for C Maximum of 3 0 vertically from the peak F Acceptable for angles 0 to 60 G Minimum of 4 for maximum refer to A and measure along slope The minimum distance between sprinklers on opposing slo...

Page 6: ...0 when minimum of 8 0 cannot be obtained due to B a baffle must be installed between these sprinklers to obstruct the discharge and prevent cold solder See B for maximum F Acceptable for angles 0 to 6...

Page 7: ...he minimum distance between sprinklers is measured horizontally Staggering sprinklers will help maintain maximum horizontal distances in difficult situations Dimension B is measured along the slope Fo...

Page 8: ...peak D Refer to Figure 8 F Acceptable for angles 0 to 60 A D C A Figure 8 Obstruction to Discharge by Intersect ing Sloped Ceiling If D is Obstructed per Figure 8 Graph then D is to be considered the...

Page 9: ...0 D in feet F in degrees Obstructed Acceptable 10 9 8 6 5 4 3 2 7 20 x 20 18 x 18 16 x 16 14 x 14 12 x 12 Figure 10 Obstruction to Discharge by an Oppos ing Sloped Ceiling If D is Obstructed per Figur...

Page 10: ...s to Heat Sources Sprinklers installed too close to heat sources can operate prematurely and so must be placed a sufficient distance away from the heat source Common heat sources in residential occupa...

Page 11: ...aced at least 3 6 ordinary temp 1 0 intermediate temp laterally from the surfaces of a stove Sprinklers must be spaced at least 1 6 ordinary temp 0 9 intermediate temp laterally from the surfaces of k...

Page 12: ...Sprinkler Guide Figure Side of open or Recessed Fireplace 36 12 Figure 14 15 Front of Recessed Fireplace 84 36 Figure 15 Coal or Wood Burning Stove 42 12 Figure 17 Kitchen Range 18 9 Figure 18 Wall Ov...

Reviews: