background image

8

Obstructions

Obstructions to Attic Sprinklers™ differ from standard sprinklers and the following criteria shall be used.

There can be up to a 6" obstruction, measured vertically, as long as it is 36", measured vertically, below the Attic
Sprinkler.  If the obstruction is closer or larger, there must be a sprinkler on the other side of the obstruction.  See figure
A & B.  This does not limit the top cord of the trusses or the depth of the rafter, but rather obstructions that run across
the trusses or rafters.

Figure B

Figure A

6" max.

No

Sprinkler

Required

36" min.

If the obstruction is below the sprinkler, there must be 6" clearance over the top of the obstruction to allow water to pass
both over and under the obstruction.  The 6" is measured perpendicular to the slope from the bottom of the joist.  If
there is not 6" clearance, a sprinkler must be added on the opposite side of the obstruction.

Figure D

Figure C

6" min.

36" min.

less than 6"

36" min.

Figure F

Figure E

36" min.

 4'-0"

No Sprinkler

Required

Ducts, as per NFPA 13, require a sprinkler under
them if they are over 4'-0" wide.  If they are not, then
no sprinkler underneath is required.

For Vertical Obstruction, See Table 1 on Page 9.
The maximum dimension of the obstruction is the
width of the obstruction and the horizontal
distance away from the obstruction is measured
flat.

See Table 1

over 6"

Sprinkler

OBSOLETE

Summary of Contents for CENTRAL Attic BB1

Page 1: ...rios Full scale tested for Listing in wood truss construction Listed for specific pitches of roof slope The Attic Sprinklers provide the best level of protection and control cost by eliminating the ne...

Page 2: ...in the attic to feed the wet system ceiling sprinklers on the floor below there must be 6 of insulation covering the pipe extending 12 on each side away from the centerline of the pipe and the area a...

Page 3: ...op of the pipe and the area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accor...

Page 4: ...40 to more than 30 35 39 0 5 6 7 12 to less than 10 12 SD3 40 to more than 30 35 39 0 5 6 10 12 to 12 12 SD1 30 to more than 10 25 20 0 5 6 4 12 to less than 7 12 SD2 30 to more than 10 25 20 0 5 6 7...

Page 5: ...al Directional Attic Sprinkler Branch Line Ceiling Truss Ridge 4 0 minimum 6 0 maximum Attic Sprinklers Attic Sprinkler 16 minimum 22 maximum Span Dimension Single Directional Standard Sprinkler Singl...

Page 6: ...al the maximum spacing is 6 0 and the minimum is 4 0 see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 on center covering 40...

Page 7: ...all as shown see figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 maximum 3 0 max on slope Back to Back Attic Sprinkler 6 0 Max 6 0 Max Be...

Page 8: ...low the sprinkler there must be 6 clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 is measured perpendicular to the slope from the bottom of t...

Page 9: ...ers 31 0 away from the corner Figure 14 If the attic has noncombustible insulation on the ceiling below the attic sprinklers the area of coverage is mea sured from the top of the insulation Maximum Di...

Page 10: ...or Single Directional The HIP Sprinkler is located along the slope down the hip and throws a 90 pattern toward the outside eaves This allows the water to corner the fire and control it even at far di...

Page 11: ...8 4 Attics Having HIP Roofs with the HIP Joists Parallel to Outside Wall The design area requirements of NFPA 13 shall apply to all sprinkler types see Fig 11 5 Attics having a Width Greater than 60 f...

Page 12: ...rranty Ordering Information Ordering Information When placing an order indicate the full product name Please specify the quantity model style orifice size temperature rating type of finish or coating...

Reviews: