background image

6

Design Guidelines

To design a project with attic sprinklers use these steps as a guideline:

•  Determine if single, dual directional or hip sprinkler is needed.
•  Determine the roof slope is between 4:12 to 12:12.  If more than one

slope is being used on a project, select the correct sprinkler for each
area.

•  Follow the guidelines for each type of sprinkler as follows:

For Back to Back™ 

(dual directional)

•  Determine the throw needed 

(see spacing requirements on page 3).  If

over 20'-0" up to 60'-0" is required, use the 

17

32

" orifice back to back™

dual directional to reduce the pressure required, or if pressure is not a
concern, use the 

1

2

" to minimize over discharge.

•  If less than 20'-0" is required, use the 

1

2

" orifice back to back™ dual

directional to minimize pressure and flow requirements.

•  Determine the distance along the slope.  If the distance is not equal,

use the longer side.  Multiply the longer side by two to determine the
spacing down the slope.  400 divided by this will determine the
maximum spacing along the ridge.  The maximum is 6'-0".  For
example, a 12:12 slope at the maximum span of 60 feet will produce a
slope length of approximately 42.5 feet.  That number multiplied by
two produces a 85' throw.  400 square feet maximum divided by an
85' throw only allows a 4'-8" spacing along the ridge.  Using the
maximum spacing, space the sprinklers along the ridge.

•  Avoid obstructions as shown on page 7.  If necessary, add standard

sprinklers to maintain coverage around obstructions.

•  Calculate the sprinkler system in accordance with the appropriate flow

and pressure information on page 3.  There is no interpolation of the
flows and pressures shown on the chart.

For Single Directional™

•  Determine the throw needed.
•  As the 400 square feet is not a factor with the Single Directional™, the

maximum spacing is 6'-0" and the minimum is 4'-0" 

(see figures 2

&11).  (The reason 400 square feet is not an issue with the single
directional™ is because at its maximum spacing, 6'-0" on center/
covering 40'-0" flat/a 12:12 slope/and the throw being 56.5 feet, the
400 square foot maximum would not be exceeded.)

•  Avoid obstructions as shown on page 7.  If necessary, add standard

sprinklers to maintain coverage around obstructions.

•  Calculate the sprinkler system in accordance with the appropriate flow

and pressure information on page 3.  There is no interpolation of the
flows and pressures shown on the chart.

For HIP™ Sprinkler 

(see figure 11)

•  Verify framing direction is perpendicular to outside wall 

(see figures 11

& 12).  If not, cover that area with standard sprinklers.

•  From the intersection of the top of the hip and the ridge the maximum

distance down the slope of the hip is 3'-0".  Start the layout with the
first sprinkler as close to that point as possible, but no further, while
staying 6" away from the face of the trusses.  Remember the slope of
the hip is not equal to the slope of the roof from the ridge to the
outside wall.  Continue to space sprinklers down the hip at a
maximum of 6'-0" on center as measured along the slope of the hip.
When the bottom of the hip is encountered, the last sprinkler must be
within 7'-6" of the outside wall as measured flat (plan view).  If this
pipe is “cut to fit” remember to take into account the different slopes
the hip and the roof as well as distances measured along the slope
verses horizontal in plan view.

•  Avoid obstructions as shown on page 7.  If necessary, add standard

sprinklers to maintain coverage around obstructions.

Figure 7

Figure 8

Figure 9

Insulation of piping is for

fire protection, not

freeze protection.

Branch Line

Ceiling

Truss

Ridge

6"

minimum

6"

OR

6"

CPVC

Non-Combustible Insulation

Non-Combustible

Insulation

Figure 10

Attic

Sprinkler

6" max.

6"

Insulation

1'-0"

1'-0"

Joist

Non-Combustible Insulation

OBSOLETE

Summary of Contents for CENTRAL Attic BB1

Page 1: ...rios Full scale tested for Listing in wood truss construction Listed for specific pitches of roof slope The Attic Sprinklers provide the best level of protection and control cost by eliminating the ne...

Page 2: ...in the attic to feed the wet system ceiling sprinklers on the floor below there must be 6 of insulation covering the pipe extending 12 on each side away from the centerline of the pipe and the area a...

Page 3: ...op of the pipe and the area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accor...

Page 4: ...40 to more than 30 35 39 0 5 6 7 12 to less than 10 12 SD3 40 to more than 30 35 39 0 5 6 10 12 to 12 12 SD1 30 to more than 10 25 20 0 5 6 4 12 to less than 7 12 SD2 30 to more than 10 25 20 0 5 6 7...

Page 5: ...al Directional Attic Sprinkler Branch Line Ceiling Truss Ridge 4 0 minimum 6 0 maximum Attic Sprinklers Attic Sprinkler 16 minimum 22 maximum Span Dimension Single Directional Standard Sprinkler Singl...

Page 6: ...al the maximum spacing is 6 0 and the minimum is 4 0 see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 on center covering 40...

Page 7: ...all as shown see figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 maximum 3 0 max on slope Back to Back Attic Sprinkler 6 0 Max 6 0 Max Be...

Page 8: ...low the sprinkler there must be 6 clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 is measured perpendicular to the slope from the bottom of t...

Page 9: ...ers 31 0 away from the corner Figure 14 If the attic has noncombustible insulation on the ceiling below the attic sprinklers the area of coverage is mea sured from the top of the insulation Maximum Di...

Page 10: ...or Single Directional The HIP Sprinkler is located along the slope down the hip and throws a 90 pattern toward the outside eaves This allows the water to corner the fire and control it even at far di...

Page 11: ...8 4 Attics Having HIP Roofs with the HIP Joists Parallel to Outside Wall The design area requirements of NFPA 13 shall apply to all sprinkler types see Fig 11 5 Attics having a Width Greater than 60 f...

Page 12: ...rranty Ordering Information Ordering Information When placing an order indicate the full product name Please specify the quantity model style orifice size temperature rating type of finish or coating...

Reviews: