Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar) 

2-1/2, 4, 6 & 8 Inch (DN65, DN100, DN150 & DN200)  

Vertical or Horizontal* Installation

Worldwide 

Contacts

www.tyco-fire.com

Page 1 of 20 

 SEPTEMBER 2014 

TFP910

General 

Description

The TYCO Model AV-1-300 Alarm 

Check Valves are divided seat ring, 

rubber-faced clapper, waterflow alarm 

check valves that are intended for 

use in wet pipe (automatic sprinkler) 

fire protection systems. They may be 

installed vertically or horizontally*, 

and they are designed to automati-

cally actuate electric and/or hydraulic 

alarms when there is a steady flow of 

water into the system that is equivalent 

to the discharge rate of one or more 

sprinklers.
A separately ordered Model RC-1 

Retard Chamber (Ref. Technical Data 

Sheet TFP920) is required for installa-

tions subject to variable pressures. It is 

used to help prevent false alarms asso-

ciated with pressure variations in public 

water supplies.
The AV-1-300 Alarm Check Valve Trim 

includes pressure gauges to monitor 

system pressure conditions, a bypass 

check valve, a main drain valve, and 

an alarm test valve. The bypass check 

valve reduces the possibility of false 

alarms by permitting slow as well as 

small transient increases in water sup-

ply pressure to be passed through to 

the system without opening the water-

way clapper.

NOTICE

The TYCO Model AV-1-300 Alarm 

Check Valves described herein must 

be installed and maintained in com-

pliance with this document, as well as 

with the applicable standards of the 

National Fire Protection Association 

(NFPA), in addition to the standards of 

any authorities having jurisdiction. Fail-

ure to do so may impair the integrity of 

these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating 

condition. Contact the installing con-

tractor or product manufacturer with 

any questions.

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved

Working Water Pressure Range

20 to 300 psi (1,4 to 20,7 bar)

Friction Loss

Refer to Graph A.

End Connections

Groove x Groove 

Flange x Groove 

Flange x Flange 

Refer to Table A for size applicability

Weights

Refer to Table A.

Physical Characteristics

The body is ductile iron, the hand-hole 

cover is ductile iron, and the seat ring 

is bronze. The clapper for the 2-1/2 

inch (DN65) valve size is stainless steel. 

The clapper for the larger valve sizes 

is ductile iron. All valve sizes utilize an 

EPDM clapper facing.
Flanged connections are available 

drilled per ANSI, ISO, AS, and JIS 

specifications as detailed in Table B.
Threaded port connections for the 

AV-1-300 Valves are available NPT 

threaded or threaded per ISO 7-1 as 

detailed in the Ordering Procedure sec-

tion. Valves with NPT threaded ports 

will readily accept the trim arrange-

ments detailed in Figures 4 through 6.

* 4, 6, and 8 inch (DN100, DN150, and DN200) valve sizes 

For Fire Protection pressure rating, listing  

and approval information, contact  

your Tyco Representative.

Summary of Contents for AV-1-300

Page 1: ...herein must be installed and maintained in com pliance with this document as well as with the applicable standards of the National Fire Protection Association NFPA in addition to the standards of any...

Page 2: ...es 4 6 8 Inch NR Clapper See b 92 200 1 423 92 200 1 623 92 200 1 823 Hex Bolt Handhole Cover 2 1 2 Inch Valve x 1 1 4 Long CH DESCRIPTION REF VALVE PARTS 1 2 13 UNC 2A 6 Inch Valve x 1 3 4 Long CH 1...

Page 3: ...95 0 0 91 23 0 11 42 290 0 5 50 139 7 0 75 19 0 5 00 127 0 5 51 140 0 0 87 22 0 0 71 18 0 0 71 18 0 0 87 22 0 0 87 22 0 0 71 18 0 0 75 19 0 4 Inch DN100 6 Inch DN150 8 Inch DN200 2 1 2 Inch DN65 4 8 8...

Page 4: ...e TYCO Model AV 1 300 Alarm Check Valves consideration must be given to the dis posal of the large quantities of water that may be associated with draining the system or performing a flow test Valves...

Page 5: ...ch line at the point most remote from the alarm valve The vent line should be connected to the top of a cross main or to the end of a branch line and be located at the highest level of a multi level i...

Page 6: ...ple 1 4 x 2 1 2 Nipple CH DESCRIPTION 1 1 4 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER...

Page 7: ...2 1 2 x 4 1 2 All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION...

Page 8: ...ESCRIPTION CH CH CH CH CH CH P N CH 1 2 x 1 2 x 3 4 Tee All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware 2 INCH NPT CON...

Page 9: ...6 048 1 007 92 304 1 017 P N 1 4 90 Elbow 1 4 Plug CH CH All Fittings and Nipples are galvanized Standard Order CH Common Hardware NOTES 1 2 SUPPORT BRACKET SUPPORT BAR EXTERNAL BY PASS TUBE ALARM TES...

Page 10: ...ommon Hardware Select Appropriate Nipple Sizes per AV 1 Alarm Check Valve Size 4 Inch DN100 29 1 2 x 1 1 2 30 1 2 x 3 1 2 Nipple Number 1 2 x 2 1 2 1 2 x 4 1 2 6 Inch DN150 2 INCH NPT CONNECTION TO DR...

Page 11: ...3 4 Tee 1 2 x 1 1 2 Nipple CH All Fittings and Nipples are galvanized Standard Order Install subassemblies in alphabetical order NOTES 3 1 2 CH Common Hardware DRIP FUNNEL 2 INCH NPT CONNECTION TO DRA...

Page 12: ...TION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM 3 4 INCH NPT CONNECTION FOR WATER MOTOR ALARM...

Page 13: ...CH CH CH CH CH CH CH CH CH CH P N 2 INCH NPT CONNECTION TO DRAIN 1 2 INCH NPT CONNECTION FOR WATERFLOW PRESSURE ALARM SWITCH RESTRICTION ASSEMBLY SEE FIGURE 3 3 4 INCH NPT CONNECTION FOR WATER MOTOR A...

Page 14: ...7 8 225 G F E D G x G F x G C A B F x G G x G B A D E C F G With RC 1 D E F G B C Dimension A Without RC 1 Dimensions in Inches and mm 16 1 2 419 8 7 8 225 10 1 2 267 12 1 4 311 16 1 2 419 10 1 2 267...

Page 15: ...2 394 12 1 2 318 10 1 4 260 10 1 2 267 10 1 2 267 10 254 10 254 19 483 D F x G F G E D F x F D G x G C A B 11 1 2 292 11 1 4 286 11 1 2 292 12 1 4 311 2 3 4 70 15 1 2 394 12 305 12 305 12 1 4 311 11 1...

Page 16: ...38 19 1 2 495 14 356 C B A E G F G F C A B B C D E G x G F x F F x G E 3 1 2 89 15 1 2 394 16 1 2 419 16 1 8 410 18 1 2 470 3 1 2 89 N A 16 1 2 419 16 1 8 410 15 3 4 400 14 356 12 305 14 356 12 305 D...

Page 17: ...es to flow from the alarm line drain Step 6 Clean the 1 2 inch Strainer located in the valve trim as well as the 3 4 inch Strainer located at the connection to the water motor alarm as applicable Be s...

Page 18: ...lve slowly remove the plug from the supply pres sure gauge test valve to relieve the supply pressure and then slowly open the union in the externally mounted bypass Step 3 Check for leakage past the B...

Page 19: ...057 8 Inch P N 52 204 4 058 Accessories Order the following accessories as applicable Model RC 1 Retard Chamber P N 52 211 1 002 Required for variable pressure water sup ply conditions Alarm Vent Tri...

Page 20: ...N 52 203 4 715 JIS Flange x 6 62 inch 168 3 mm Groove O D P N 52 203 4 815 JIS Flange x 6 50 inch 165 1 mm Groove O D P N 52 203 5 815 6 50 inch 165 1 mm Groove O D x 6 50 inch 165 1 mm Groove O D P N...

Reviews: