SOLARLOK Interconnection System

2-1773458-2 

Issued 8-2010

Installation Manual

tycoelectronics.com/solar

All specifications subject to change. Consult Tyco Electronics for latest specifications.

1

(2)

(3)

(2

)

(3)

(1)

(2)

(3)

(4)

1.  Safety Note

■ 

 The SOLARLOK connector is to be used only to  
interconnect firmly fixed cables.

■   

Do not disconnect under electrical load!

■   

Electrical current path should only be disconnected  
using approved devices.

■ 

 Only cables released from Tyco Electronics are permitted 
to be used with SOLARLOK component cable assemblies.

■   

SOLARLOK component cable shall be labelled with label  
PN 1718077-1 “Do not disconnect under load”.

■   

To protect against shock, ensure that conductors and 
their associated connectors are separated from opposite 
polarity components.

■   

Unconnected connectors 

must

 always be protected from 

pollution (e.g. dust, humidity, foreign particles, etc.), pri-
or to installation. Do not leave unconnected (unprotect-
ed) connectors exposed to the environment. The usage 
of TE connector dust caps is strongly recommended.

■   

Connectors that are unmated in the field should also be 
protected from pollutants.

■   

Do 

NOT

 use any 

oil or lubricants

 during mounting.

2.  Tools

(1) Stripping Tool

1.5 mm

2

 – 6.0 mm

2

, 10 AWG

PN 4-1579002-2

(2) Crimping Tool

4.0 mm

2

 and 6.0 mm

2

, 10-12 AWG PN 1-1579004-2

(3) Extraction Tool

all terminals

PN 1102855-3

(4) Field Service Kit

all in one

PN 1534858-1

!