background image

Do

•  Store the sensing cable in its original container in a clean, dry area prior 

to installation.

•  Schedule sensing cable installation after pipe is assembled and pressure 

tested.

•  Install alarm module first, then install sensing cable from the module 

outward.

•  Clean the area where the cable will be installed, to remove debris and 

sources of contamination.

•  Install sensing cable before burying pipe.

•  Provide “as built” drawings to facilitate completion of a system map.
•  Replace TT5000 sensing cable once it has contacted a solvent or fuel.

Don’t

•  Drag the cable through contaminants (such as pipe dope, PVC cement, 

alcohol, oil, dirt).

•  Use damaged or contaminated sensing cable.

•  Solder or weld near the cable without protecting it from heat, flux, and 

splatter.

•  Use pulling lubricants to install TraceTek cables.

•  Drop tools, or sharp or heavy objects onto the cable.

•  Pull sensing cable with excessive force (more than 50 pounds /20 kg for 

TT5000, more than 75 pounds/30 kg for TT3000).

•  Pull bulk TT5000 sensing cable without sealing its end.

•  Place TT5000 sensing cable where it is subject to pinching or 

temperatures above 60°C (140°F).

•  Leave TT5000 sensing cable installed under tension.

•  Use adhesive tapes or clamping devices to permanently secure the 

sensing cable.

•  Allow cable ends to become wet, dirty, or contaminated.

GENERAL NOTES—DO’S AND DON’TS

TT3000 and TT5000 Series

Bulk Sensing Cable Installation Instructions

GENERAL INFORMATION

These instructions detail techniques used to install nVent RAYCHEM 

TraceTek TT3000 or TT5000 bulk sensing cable into double-containment 

pipe. Installation is made from pull point (access tee) to pull point. Two 

people, the feeder and the puller, are needed to complete the installation. 

They must be able to communicate at all times during the installation. 

Two-way radios may be required. These instructions assume that 1/4-

inch or 3/8-inch hollow braid pull rope has been installed according 

to the TraceTek Double Containment Installation Guide (LIT-138). To 

ensure that the pipe is cable ready, see the TraceTek Products Selection 

Guide (H54783), Section 2. After the cable has been installed, use the 

connector installation instructions included in connector kits for nVent 

RAYCHEM TraceTek TT3000 and TT5000 sensing cables (TT-3000-CK-

MC-xxx or TT-5000-CK-MC-xxx). For more information call (650) 216-

1526.

TOOLS AND MATERIALS NEEDED

•  Ohmmeter (20 MΩ range or greater)
•  Kellems grip (TT-KELLEM-GRIP)
•  Reel mounting stand (to allow reel to spin and pay off sensing cable; 

see page 4)

•  Two lengths of 3/4-inch electrical conduit bent to a gentle sweep. 

These must be longer than the highest riser (the vertical pipe section 

at access tees), flared slightly, and deburred at both ends (see Step 4 

on page 4).

•  Electrical tape

IN ADDITION, FOR INSTALLING TT5000 SERIES 

SENSING CABLES:

•  TT-ULTRATORCH flameless heating tool or appropriate heat gun
•  Pliers (to crimp heat-shrinkable tubing)
•  Masking tape

Содержание TraceTek TT3000 SERIES

Страница 1: ...00 Series Bulk Sensing Cable Installation Instructions GENERAL INFORMATION These instructions detail techniques used to install nVent RAYCHEM TraceTek TT3000 or TT5000 bulk sensing cable into double containment pipe Installation is made from pull point access tee to pull point Two people the feeder and the puller are needed to complete the installation They must be able to communicate at all times...

Страница 2: ...ugh to fully recover the tubing but not so long as to melt the braid do not apply heat directly on the braid and if braid is damaged begin again In the middle of the tube continue heating for 10 to 15 seconds after the tubing has shrunk to ensure adhesive in the tubing bonds to the cable jacket Shrink the entire tube finishing at the end off the cable 6 While the tubing end is still hot use pliers...

Страница 3: ...d locating module 2 Attach Kellems grip to sensing cable 1 Make sure the end of the sensing cable has been properly prepared end of TT5000 sensing cable should be sealed with heat shrink tubing end of TT3000 should be wrapped tightly with electrical tape 2 Insert the end of the cable as far as possible into the cage end of the Kellems grip 3 Tightly wrap electrical tape over 1 in 25 mm of the Kell...

Страница 4: ...pipe Use the conduit section to guide the pull rope and sensing cable out of the pipe position it to avoid sharp bends abrasion and snags 5 Pull sensing cable into containment pipe 1 Hold the conduit in position while pulling the cable Begin to pull the rope and cable from the second access point The person feeding the cable must be able to communicate problems such as snags or twisted cable to th...

Страница 5: ...till below 20 MΩ it may indicate the cable is bent or crimped which simulates a leak or the cable has been tripped by exposure to a hydrocarbon such as oil or adhesive or the jacket has been damaged and allowed water to enter the braided inner construction A TraceTek Portable Test Box TT PTB 1000 may be used to determine the location of the problem contact your RAYCHEM representative for further i...

Страница 6: ...1 5426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com nVent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notice RaychemTraceTek IM H55553 TT3000TT5000Bulk EN 1...

Отзывы: