M.E-2009.E-1DB2
3/25/07 – rev. 5/28/09
E-1DB2 CONTROLLER
2.3.1 Connect
the
BLACK
wire from the photocell to TB1-8.
2.3.2 Connect
the
RED
wire from the photocell to TB1-9.
2.3.3 Connect
the
WHITE
wire from the photocell to TB1-10.
2.3.4 Install the photocell into the receptacle and twist to the right while depressing
to lock into place.
2.4
POWER WIRING
(Refer to Drawing H40-329)
Power wiring to the control cabinet should be in accordance with local methods and
the National Electric Code (NEC).
2.4.1 A 15 amp circuit breaker is recommended at service panel.
2.4.2 Connect the "HOT" side of the 120V AC line to TB1-11.
2.4.3 Connect the "NEUTRAL" side of the 120V AC line to TB1-12.
2.4.4 Connect the AC ground to the ground stud to the lower right of the terminal
block TB1.
2.4.5 Controller panel should be connected to the tower and/or building grounding
system with the exception of installations on AM RF Applications where
controller grounding to earth ground is prohibited. Ground the controller only
to the tower itself using a suitable RF ground.
2.5
TOWER LIGHTING KIT
When installing this system, the customer will need to use strobe cable wiring
method to wire the strobe beacon. Refer to drawing 600-04 for cable installations.
3
Summary of Contents for E-1DB2
Page 18: ...M E 2009 E 1DB2 3 25 07 rev 5 28 09 13 ...
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......