background image

 DDS EX

 

Explosion-Proof Transmitter and Controller Instruction Manual

 

 

19 

Using

 

P

RO

V

Serial Adapters  

 

 

NOTICE

 

P

RO

V

U

 expansion modules and serial adapters are not included in 

the hazardous area approvals of the DSS EX. The PDA1232 may 

be used only while the DSS EX is in a safe area, and will disable 

some features while installed. 

 

P

RO

V

expansion modules and serial adapters are not recommended for use with the DSS EX. It is 

recommended that any serial protocol conversion required on the RS-485 communications connection be 

performed using a PDA7485 RS-232 to RS-485 or PDA8485 USB to RS-485 serial converter located in a 

safe area. 

F4 Digital Input Connections 

 

A digital input, F4, is standard on the scanner. This digital input connected with a normally open closure 

across F4 and COM, or with an active low signal applied to F4. 

 

 

 

Figure 9. F4 Digital Input Connections 

 

Relay Connections 

Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on the back of the 

scanner. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) 

contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM 

(common) terminal of the INPUT SIGNAL connector. 

 

Figure 10. Relay Connections

 

 

 

!

P-

F4

P+

COM V+

3

4

1

2

5

mA+ COM V+ mA+

7

8

6

9

Ack

C

NO

NO

NC

NC

C

RELAY4

RELAY3

4

3

6

5

2

1

C

NO

NO

NC

NC

C

RELAY2

RELAY1

4

3

6

5

2

1

Summary of Contents for PD8-6080-6H0-TU

Page 1: ...Inputs Math functions Capabilities Isolated 24 VDC 25 mA Transmitter Power Supply Multi Pump Alternation Control Signal Input Conditioning for Flow Round Horizontal Tank Programmable Displays Function...

Page 2: ...liable for damages resulting from such improper use Failure to follow installation guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Never...

Page 3: ...ting Up the Process Variables PVs pv setup 37 Setting the Display Decimal Point disp dp 37 Setting the Float Decimal Point Flot dp 37 Scaling the PV Display Values sCale 38 Scale Menu 38 Setting Up th...

Page 4: ...Service 81 Mounting Dimensions 81 EU Declaration of Conformity 82 Table of Figures Figure 1 Transmitter Supply Voltage Selection 14 Figure 2 Integrated ProVu Required Connections 15 Figure 3 Connecto...

Page 5: ...ut Data is displayed on an adjustable intensity dual line six digit display Its superluminous LED digits make it easily readable in smoke dust fog and direct sunlight The upper display is a 0 6 inch s...

Page 6: ...output PD8 6080 7H0 TU TT DSS 6080EX DC Explosion Proof Transmitter for DSS Smart Digital MODBUS RTU sensors powered 12 24 VDC No options PD8 6080 7H7 TU TT DSS 6080EX CC RM Explosion Proof Controller...

Page 7: ...tion break condition The master polls the slave 3 times before starting the response timeout timer Slave Snooper mode Time the scanner will wait for new data before going into break condition Slave mo...

Page 8: ...lay Max min readings are stored until reset by the user or when power to the scanner is turned off User can reset by front panel pushbuttons digital input or via Modbus registers Password Three progra...

Page 9: ...for each relay Note Relay coil is energized in non alarm condition In case of power failure relay will go to alarm state Auto Initialization When power is applied to the scanner relays will reflect t...

Page 10: ...lation Multi Point Linearization 2 to 32 points for PV1 and PV2 Programmabl e Exponent 1 0001 to 2 9999 Low Flow Cutoff 0 999999 0 disables cutoff function for PV1 and PV2 Calibration Range Input Rang...

Page 11: ...C T5 40 C to 65 C Certificate number Sira 12ATEX1182 IECEx Ex d IIC T Gb Ex tb IIIC T90 C Db IP68 Ta 40 C to C T6 40 C to 60 C T5 40 C to 65 C Certificate Number IECEx SIR 12 0073 Special Conditions...

Page 12: ...005 EMC heavy industrial generic immunity standard RFI Amplitude Modulated 80 1000 MHz 10 V m 80 AM 1 kHz 1 4 2 0 GHz 3 V m 80 AM 1 kHz 2 0 2 7 GHz 1 V m 80 AM 1 kHz Electrical Fast Transients 2kV AC...

Page 13: ...ith applicable local and national regulations e g NEC For Installation in USA The DSS EX must be installed in accordance with the National Electrical Code NEC NFPA 70 For Installation in Canada The DS...

Page 14: ...he instrument is in service Cover Jam Screw The cover jam screw should be properly installed once the instrument has been wired and tested in a safe environment The cover jam screw is intended to prev...

Page 15: ...the back of the electronics module Some connectors may be provided already connected These connections are required for proper operation of the DSS EX and should not be removed unless instructed to by...

Page 16: ...s cables or scanners to the RJ45 M LINK connector Otherwise damage will occur to the equipment and the scanner Figure 3 Connector Labeling for Fully Loaded DSS EX Power Connections Power connections a...

Page 17: ...S EX has three diagnostic LEDs a Power P LED to show when the module is powered properly a Transmit Data TX LED to show when the module is being transmitted to by the PC side and a Receive Data RX LED...

Page 18: ...o the meter and ensure personnel safety Notes 1 Termination resistors are optional and values depend on the cable length and characteristic impedance Consult the cable manufacturer for recommendations...

Page 19: ...5 serial converter located in a safe area F4 Digital Input Connections A digital input F4 is standard on the scanner This digital input connected with a normally open closure across F4 and COM or with...

Page 20: ...oad Experiment for best results Figure 12 Low Voltage DC Loads Protection RC Networks Available from Turtle Tough RC networks are available from Turtle Tough and should be applied to each relay contac...

Page 21: ...anel LED flashes when locked out The interlock relay would be wired in series with the load N O contact See below Figure 14 Interlock Connections Analog Input Signal Connections Analog input signal co...

Page 22: ...use The display may or may not show a fault condition depending on the nature of the overload The fuse limits the current to a safe level when it detects a fault condition and automatically resets its...

Page 23: ...equirements and applicable national state and local codes to prevent damage to the meter and ensure personnel safety External Switch Contacts The DSS EX includes 4 digital inputs These digital inputs...

Page 24: ...tract finger more than three inches from the glass before pressing the next button When the cover is removed the four mechanical buttons located next to the sensors are used The sensors are disabled w...

Page 25: ...nds Notes F4 is a digital input Press the Menu button to enter or exit the Programming Mode at any time Press the Right arrow button to move to the next digit during digit or decimal point programming...

Page 26: ...ions until you see one of the dialogs below If you receive a User Account Control warning click Yes 4 If there is an update available click the Update button to install the new version Otherwise click...

Page 27: ...teger t poll Polling Time Enter Polling Time the time between read commands In other words how often the display is updated in Master mode Display Parameter Action Setting Description t resp Response...

Page 28: ...s of an Inch dec Decimal Decimal Format Display Parameter Action Setting Description Ft In 8 Eighths Eighth Inch Format Ft In 16 Sixteenths Sixteenth Inch Format Dec Pt Decimal Point Decimal Point men...

Page 29: ...off when Communications Break detected Aout Analog output Enter the Analog Output scaling menu AOut 1 Aout channel Analog Output source channel 1 3 Display Parameter Action Setting Description Dis 1 D...

Page 30: ...ng changed is displayed brighter than the rest Press and hold the Up arrow to auto increment the display value Press the Enter button at any time to accept a setting or the Menu button to exit without...

Page 31: ...r When using more than one scanner in a multi drop mode each scanner must be provided with its own unique address The scanner address Scan ID may be programmed between 1 and 247 The transmit delay may...

Page 32: ...er Mode navigate to the PV Number menu and press ENTER From there the user can scroll through all of the sixteen available PVs In order to enable a specific PV simply press ENTER to access the desired...

Page 33: ...byte order Poll Time Enter the time interval to poll the slave devices selected Response timeout Enter the time interval to wait after three polls before reporting it as a Communications Break Back To...

Page 34: ...s e g 4800 bps or less 2 The response time for scanners set up for Snooper mode must be greater than the Master s poll time This setting corresponds to the time window during which the Snooper listens...

Page 35: ...Default Slave ID for PV1 001 for PV2 002 for PV3 003 etc The Master ignores the decimal point setting for slave devices that specify a Short or Long integer For example a slave that is displaying 12...

Page 36: ...Point d Scale input data 2 Display assignment Intensity 3 Relay assignment and operation 4 4 20 mA analog output scaling Press the Menu button to exit at any time Aout Menu will only display if enabl...

Page 37: ...ight until no decimal point is displayed and then it moves to the leftmost position The decimal point is programmable only for the Display Value Setting the Float Decimal Point Flot dp If floating poi...

Page 38: ...or Programmable Exponent functions Round Horizontal Tanks are scaled using the length and diameter of the tank Scale Menu The display will show Error if the scaling or calibration process is unsuccess...

Page 39: ...an be programmed to display any of the following Display Parameter Setting Description D pv Display PV Display PVs 1 16 D Ch C Display C Channel Display Math Channels C1 C4 Pv unit Display PV Units Di...

Page 40: ...Note For Tag PVn and Tag PVn U the default settings for PVs are 1 3 5 7 followed by two underscores which represent empty PVs These all can be changed to any enabled PVs Continues to Relay Setup Line...

Page 41: ...or Tag PVn and Tag PVn U the default settings for PVs are 2 4 6 8 followed by two underscores which represent empty PVs These all can be changed to any enabled PVs Continues to Display Intensity Setup...

Page 42: ...7 7 H H q q 8 8 h h r r 9 9 I I s S A A I i t t Degree b b j J u u Space Notes Degree symbol represented by if programming with ScanView The letters m and w use two 7 segment LEDs each when selected...

Page 43: ...inary Signed Long Byte Order 1234 1234 PV4 Slave ID 2 2 Function Code 04 04 Register PV4 30001 30001 Tank 2 Product Level Data Type Long integer Binary Signed Long Byte Order 1234 1234 PV5 Slave ID 2...

Page 44: ...3 30003 Tank 4 Interface Data Type Long integer Binary Signed Long Byte Order 1234 1234 PV12 Slave ID 4 4 Parameter DSS EX Master DSS EX Snooper Description Comment Function Code 04 04 Register PV12 3...

Page 45: ...r alarm condition has cleared e Pump alternation control automatic reset only f Sampling the relay is activated for a user specified time g Off relay state controlled by Interlock feature 3 Set 1 Set...

Page 46: ...ow reset point The deadband is defined as the difference between set and reset points Minimum deadband is one display count If the set and reset points are programmed with the same value the relay wil...

Page 47: ...mmed to go to one of the above conditions when the scanner detects the loss of the input signal i e 0 005 mA Notes 1 This is not dependent on the Communications Break or Response Timeout setting 2 Thi...

Page 48: ...on Set Reset Note Relay coil is energized in non alarm condition In case of power failure relay will go to alarm state Low Alarm with Fail Safe Operation Set Reset Note Relay coil is energized in non...

Page 49: ...an be programmed to react to this event by going On Off or No Action After communication is restored the relays are turned off or on based on their operating mode and their set and reset points withou...

Page 50: ...e following graphs show the operation of the time delay function When the signal crosses the set point the On time delay timer starts and the relay trips when the time delay has elapsed If the signal...

Page 51: ...to the scanner is off Front Panel LEDs The LEDs on the front panel provide status indication for the following The scanner is supplied with four alarm points that include front panel LEDs to indicate...

Page 52: ...on Latching Relay LatcH In this application the scanner is set up for manual reset at any time Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off the L...

Page 53: ...t the first pump on is the first pump off Application 1 Pump Alternation Using Relays 1 2 1 Relays 1 and 2 are set up for pump alternation 2 Relays 3 and 4 are set up for low and high alarm indication...

Page 54: ...he corresponding digital input dI 1 to dI 4 terminal Interlock Relay Operation Example Relays 1 2 are configured to energize their front panel LEDs are off when SW1 SW2 switches above are closed If th...

Page 55: ...g Output Source Programming on page 70 No equipment is needed to scale the analog outputs simply program the display values to the corresponding mA output signal The Analog Output menu is used to prog...

Page 56: ...yed and enter the correct password to gain access to the menu After exiting the programming mode the scanner returns to its password protected condition Disabling Password Protection To disable the pa...

Page 57: ...7 User Programming for function keys and digital I O 8 Analog Channels Input Calibration 9 System Information Advanced Menu Navigation Tips Press and hold the Menu button for three seconds to access...

Page 58: ...ate input 1 signal or program input 1 value Dis 1 Display 1 Program display 1 value Inp 2 Input 2 Calibrate input 2 signal or program input 2 value up to 32 points for PV1 PV2 Display Parameter Action...

Page 59: ...Points 1 8 Set Points 1 8 Rly d Relay Disable Relay Disable all relays Rly e Relay Enable Relay Enable all relays O Hold Output Hold Output Hold all relays d Hold Display Hold Display Hold while held...

Page 60: ...nd remain there until the operator manually advances to the next PV or returns to the previous PV If a new alarm is detected the process is repeated The scanner ignores old alarms Control Menu Contrl...

Page 61: ...ayed immediately by setting the bypass value accordingly If the input signal goes beyond the bypass value it will be displayed immediately with no averaging done on it The noise filter bypass value ma...

Page 62: ...ovides a display that is linear with respect to the input data e g 0 000 0 000 10 000 10 000 and then 5 000 5 000 Linear Function Menu Linear Scanners are set up at the factory for linear function wit...

Page 63: ...maximum flow Programmable Exponent Function Menu prog e The programmable exponent function is used to calculate open channel flow measured with a level transmitter in weirs and flumes The flow rate is...

Page 64: ...any engineering unit without the need to re enter the dimensions again Changing the Volume from Gallons to Liters In the graphic entering the 48 for the diameter and 120 for the length of the round ho...

Page 65: ...P F diFAbS Average PV1 PV2 2 P F AvG Multiplication PV1 PV2 P F Nmulti Division PV1 PV2 P F divide Max PV Max value of all selected PVs Hi pv Min PV Min value of all selected PVs Lo pv Draw PV1 PV2 1...

Page 66: ...8 Please refer to the following graphics for details on various Math Functions Main Math Channels Each PV is represented by an underscore There are 6 lines shown and ten lines hidden Enter any or all...

Page 67: ...smitter and Controller Instruction Manual 67 Sum Menu sunm Difference Menu dif Difference Absolute Menu difAbS Average Menu avg Multiplication Menu nmulti Divide Menu divide Only two PVs at a time wil...

Page 68: ...Lo pv Draw Menu drauw Only two PVs at a time will be used for this function Weighted Average Menu uwAvg Only two PVs at a time will be used for this function Ratio Menu ratio Only two PVs at a time w...

Page 69: ...r to be programmed so that the often unsteady output from a differential pressure transmitter at low flow rates always displays zero on the scanner The cutoff value may be programmed from 0 to 999999...

Page 70: ...utputs follow the graphic above The overrange and underrange values are the values that will be output when the display shows an overrange or underrange condition This setting is common to all analog...

Page 71: ...all channels Rst HL Reset the stored maximum minimum display values for all channels relay Directly access the relay menu Set 1 Directly access the set point menu for relay 1 through 8 Rly d Disable...

Page 72: ...o take you to the next level then pressing the Up arrow until you arrive at the RESET menu Press ENTER to assign the RESET menu to the selected function key or digital input Now when the scanner is in...

Page 73: ...ter 4 The display will show 4 nmA The DSS EX mA output should now be close to 4 mA Press Enter and the display will show 04 000 Enter the actual value read by the digital mA meter and press Enter 5 Th...

Page 74: ...Menu to exit calibration without saving the changes Error Message Error An error message indicates that the calibration or scaling process was not successful After the error message is displayed the s...

Page 75: ...us Check 1 Increase Master s Transmit Delay e g Snooper delay 100ms Master delay 110ms 2 Increase Snooper s byte to byte timeout 3 Decrease the slave device s transmit delay to 10ms 4 Snooper cannot r...

Page 76: ...start the setup process from the factory defaults Instructions to load factory defaults 1 Enter the Advanced Features menu see page 57 2 Press Up arrow to go to Diagnostics menu 3 Press and hold Right...

Page 77: ...nnels which may have each performed a different Math function The dual line display can be customized by the user Typically the upper display is used to display the PV while the lower display is used...

Page 78: ...h the integrated meter The symbols by each SafeTouch button correspond to a mechanical button as shown in the above table SafeTouch Button Tips To the extent possible install the display facing away f...

Page 79: ...oint Flot dp ddd ddd Number of points No pts 2 all PVs and C channels Scaling SCalE pv 1 All Input 1 InP 1 0 000 Display 1 Dis 1 0 000 Input 2 InP 2 10 000 Display 2 Dis 2 10 000 Math channel C1 4 Sum...

Page 80: ...out Dis 1 00 00 00 Output 1 value Out 1 4 000 mA Display 2 analog out Dis 2 20 00 00 Output 2 value Out 2 20 000 mA Parameter Display Default Setting Source analog output Source PV 1 Overrange output...

Page 81: ...consistent with the appropriate hazardous locations certifications If the instrument is installed in a high voltage environment and a fault or installation error occurs high voltage may be present on...

Page 82: ...079 31 2008 EN 61000 6 4 2007 EN 61010 1 2001 and EN 61326 2006 are no longer harmonized The requirements of these standards have been checked against the harmonized standard EN 55022 2010 EN 60079 0...

Page 83: ...2 634 644 Mitcham Rd Vermont VIC 3133 Australia Phone 1 909 547 3300 Email info turtletoughsensors com www turtletoughsensors com LIM8 6080TU_A SFT088 Ver 2 000 up 02 19 How to Contact Turtle Tough Ph...

Reviews: