Operating Instructions
Before operation
28
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.1.5
Web server – login
Open the web server.
Log on to the device as administrator. The default user for the web server is ”admin”, the
default password is ”password”.
Enter user name and password in the login field on the start page of the web server.
Click
Login
.
NOTE
The password is transmitted in plain text.
Secure device access with password
NOTICE
Inadequately secured devices
Unauthorized access to sensitive data
Change password after first login. Turck recommends using a secure password.
Adapt the password to the requirements of the network security concept of the
system in which the devices are installed.
7.1.6
Configuring
The safety function of the safe channels can only be configured via the "Turck Safety Configur-
ator" software.
After configuration, the device generates a configuration protocol including CRC (PROFIsafe) or
a configuration signature and a time stamp (CIP Safety). The configuration protocol must be
checked and confirmed by the user. The CRC or the Configuration Signature and the time
stamp are stored in the configuration of the fail-safe controller as a reference and guarantee
the correct safety function.
Further information on the Turck Safety Configurator software can be found in the online help.
The configuration of the safe I/O channels set via the Turck Safety Configurator is automatically
stored on a plug-in memory chip (included in delivery). When a device is replaced, the device
configuration can be transferred to another device using the memory chip.