Addressing – TBPN-L…-FDIO1-2IOL
Setting the F address via rotary coding switches
Open the cover above the switches.
Set the F address via the three rotary coding switches under the cover at device.
Execute a power cycle.
BUS
ERR
PROFINET
ETH1
ETH2
F-Address
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
x 100
x 10
x 1
Memory
Fig. 15: Rotary coding switches at the device
In the delivery state, the rotary switches are set to 000 (0 - 0 - 0). Address 000 and addresses
≥ 900 are not valid F addresses.
Switch position
Meaning
000
Delivery state, no valid F-address
1…899
F address, accept setting by restarting the device
900
Factory Reset: Resets device to factory settings
901
Erase Memory: Deletes the content of the configuration memory