Quick Start Guide

PSU67-3P-1MP-2M5-24200-F

Other documents

The following additional documents are available online at 

www.turck.com

:

Data sheet

EU declaration of conformity (current version)

For your safety

Intended use

The power supply unit PSU67-3P-1MP-2M5-24200-F is a stand-alone power 

supply for three-phase mains systems for indoor use. 

The devices must only be used as described in these instructions. Any other 

use is not in accordance with the intended use. Turck accepts no liability for 

any resulting damage.

General safety instructions

The device must only be mounted, installed, operated and maintained by 

trained and qualified personnel.

The device is a ”Class of Protection I” equipment according to IEC 61140.

The device is designed for pollution degree 3 areas in controlled environ-

ments. 

Do not use the device without additional protective devices in the area of 

personal and machine protection.

Operate the device exclusively within the technical specifications.

Do not connect the negative potential of any output externally to PE.

Do not use without a proper PE (Protective Earth) connection.

Product description

Device overview

S. fig. 2: dimensions, s. fig. 3: block diagram

Functions and operating modes

The power supply provides a stabilized and galvanically separated PELV 

output voltage at the two outputs OUT1 and OUT2. The negative potential of 

the outputs is permanently connected to PE within the unit. 

The output is electronically protected against no-load, overload and short 

circuit and can supply any kind of loads, including unlimited inductive and 

capacitive loads. 

If capacitors with a capacitance >20 mF are connected to one output, this 

output might switch off after turning the unit or the output on or connect-

ing the load.

The device is equipped with an over-temperature protection. In case of an 

over temperature, the device shuts down and starts automatically again 

after cooling off.

In case of an internal defect, a redundant circuit limits the maximum output 

voltage to 32.5 V. The outputs are shut down and restart automatically if the 

defect is eliminated.

Mounting

General installation instructions

The enclosure of the device provides a degree of ingress protection of IP65 

and IP67 when installed with all mating connectors firmly connected.

The device is generally designed for altitudes up to 5000 m (16400 ft). Above 

2000 m (6560 ft), output current and overvoltage category must be reduced.

When using the device in TN, TT and IT networks the following applies: 

TN, TT mains systems with earthed neutral and IT star mains systems with 

insulation monitoring: Use in zones of overvoltage category III up to an 

altitude of 2000 m (6560 ft), use in zones of overvoltage category II up to 

an altitude of 5000 m (16400 ft)

TN, TT, IT delta mains systems or IT star mains systems without insulation 

monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft) 

The device uses convection cooling. An external fan is not necessary.

Mounting instructions

CAUTION

Sharp edges on the back of the device

Risk of injury

Mount the devices on a sufficiently large, even surface so that all sharp 

edges are covered.

 

Mount the device vertically with the connection level facing downwards 

on a flat surface using two screws each at the upper and lower mounting 

holes. 

 

Other mounting orientations: reduce the output current.

 

Do not obstruct airflow. Do not cover ventilation fins.

 

Observe the minimum installation clearances: 50 mm on top and bottom, 

10 mm on the front and 10 mm left and right side.

Connection

 

Connect the device according to “Wiring diagrams”.

Mating connectors 

Input voltage (XD1): 7/8” male connector, 4 pole, multi coded

Relay OK signal (X0): standard M12 female connector, 5 pole A coded

Output voltage (XD2, XD3): 7/8“ male connector, 5-pole

Suitable accessories can be found in the Turck product database at  

www.turck.com

. The accessories are not part of the scope of delivery.

 

Do not apply return voltages from the load to the outputs higher than 

35 V.

 

Do not connect outputs or devices in parallel for higher output currents.

© Hans Turck GmbH & Co. KG | 100029123 2021-04 DE EN 

PSU67-3P-1MP-2M5-24200-F

PSU67-3P-1MP-2M5-24200-F

IP67 Power Supply

Quick Start Guide

Doc-No. 100029123 2104

Additional  

information see 

180.6 [7.11"]

183.0 [7.20"]

90%
80%

60%
50%

200%
175%

Voltage

Set

OUT 1

150%
125%
100%

70%

Status

20%

OUT 2

38.0 [1.50"]

107.0 [4.21"]

58.7 [2.31"] REF

40.0 [1.57"]

80.0 [3.15"]

111.0 [4.37"]

turck.com