background image

V01.01 | 2022/03

19

9.2

Setting via FDT/IODD

The devices can be set via a PC with an FDT frame application (e.g. PACTware). All the required
Turck software components can be downloaded via the Turck Software Manager:

n

PACTware

n

IODD

n

DTM for USB-2-IOL-002 IO-Link adapter

n

IODD DTM Configurator

The Turck Software Manager can be downloaded free of charge from 

www.turck.com

.

The USB-2-IOL-002 USB IO-Link adapter (ID 6825482) is required for connecting to the PC.

A 4-pin standard sensor cable (e.g. RKC4.4T-2- RSC4.4T/TXL; ID 6625608) is required for 
connecting the sensor to the USB-2-IOL-002 IO IOL-Link adapter.

Further information on setting the devices via IODD with a configuration tool is provided in the
IO-Link commissioning manual.

9.3

Setting and visualization with the Turck Vibration Monitor

The device can be configured and tested via a Turck IO-Link master (e.g. TBEN-S2-4IOL). The
integrated web server of the IO-Link master offers access to all the parameters of the sensor
IODD. An overview of the IO-Link parameters as well as descriptions are provided in the IO-Link
parameter manual. The Turck Vibration Monitor is also available for visualizing process data.

Access to the sensor parameters and the Turck Vibration Monitor requires the connection of a
Turck IO-Link master. The following table shows the firmware version of the IO-Link masters
required for using the Turck Vibration Monitor:

IO-Link master

Firmware version

FEN20-4IOL

V1.2.0.0

TBEN-L4-8IOL

V3.3.2.0

TBEN-L5-8IOL

V3.3.2.0

TBEN-LL-8IOL

V1.1.1.0

TBEN-S2-4IOL

V3.4.1.0

Refer to the instructions for use of the relevant device for information on the Turck IO-Link 
masters.

„

Connect the IO-Link master to the power supply.

„

Connect the IO-Link master to a PC via the Ethernet interface.

„

Connect the CMVT… to an IO-Link port of the IO-Link master.

If no IO-Link master is available with the appropriate firmware version, the CMVT… can be set
via the web demo and configuration tool. This requires the use of an IO-Link adapter (e.g.
USB-2-IOL-0002; ID 6825482) for the connection between the PC and the sensor. The above-
mentioned FEN20-4IOL and TBEN… IO-Link masters can also be used with older firmware ver-
sions. The web demo and configuration tool enable access to the sensor via the local web
browser.

The web demo and configuration tool can be downloaded free of charge from

www.turck.com

.

Summary of Contents for CMVT Series

Page 1: ...Your Global Automation Partner Instructions for Use CMVT Condition Monitoring Sensors with IO Link...

Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Page 3: ...2 Properties and features 8 4 3 Operating principle 9 4 4 Functions and operating modes 9 4 4 1 IO Link mode 9 4 4 2 SIO mode standard I O mode 9 4 4 3 Measurement axes 9 4 4 4 Temperature measurement...

Page 4: ...urck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 11 Maintenance 24 12 Repair 24 12 1 Returning devices 24 13 Disposal 24 14 Technical data 25 15 Turck subsidiaries contac...

Page 5: ...m risk of death or severe injury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoided NOTICE NOTICE indicates a sit...

Page 6: ...traight 0 3 RS4 30 cm cable M12 1 receptacle 4 pin straight CM VT Functional principle Detection type V Vibration T Temperature Condition Monitoring Sensors CM VT QR20 IOL X3 H1 1 4 1 2 2 Scope of del...

Page 7: ...or condition monitoring or for predictive maintenance tasks The devices may only be used as described in these instructions Any other use is not in accord ance with the intended use Turck accepts no l...

Page 8: ...6 2 46 Fig 1 Dimensions CMVT H1141 mm Inch 14 LED 3 5 5 0 22 42 5 1 67 52 2 05 62 6 2 46 20 0 79 M12 1 21 5 0 85 71 6 2 82 L Fig 2 Dimensions CMVT 0 3 RS4 4 1 1 Indication elements The devices are pr...

Page 9: ...For this the device is integrated in the controller level via an IO Link master The communication parameters are exchanged first of all the cyclic data exchange of the process data process data objec...

Page 10: ...0 F 49 208 4952 264 more turck com www turck com 4 4 4 Temperature measurement The condition monitoring sensors can output the temperature via acyclic data and cyclic data 16 bit telegrams The measure...

Page 11: ...ink master channels protection type IP20 218 230 5 C4 C5 C6 C7 6 3 38 8 60 4 C0 C1 C2 C3 24 30 2 X2 X1 P2 P1 TBEN L4 8IOL 6814082 Compact multiprotocol I O module for Ethernet 8 IO Link master channel...

Page 12: ...al PNP channels 0 5 A channel diagnostics protection type IP65 IP67 IP69K 42 11 5 15 M12 x 1 L M12 x 1 15 49 5 18 2 RKC4 4T 2 RSC4 4T TXL 6625608 Connection cable M12 female connector straight 4 pin M...

Page 13: ...ement axes of the device to the direction of vibration Position the device as close as possible to the vibration source Clean the installation surface and the surrounding area Position the potted side...

Page 14: ...6 Connection Connect the female connector of the connection cable to the male connector of the sensor Connect the open end of the connection cable to the power supply and or processing units 6 1 Wirin...

Page 15: ...V01 01 2022 03 15 7 Commissioning After connecting and switching on the power supply the device is automatically ready for operation...

Page 16: ...9 208 4952 264 more turck com www turck com 8 Operation 8 1 LED display LED Color Meaning PWR IOL Green Device is operational Green flashing IO Link communication active Out 1 Yellow Out 1 switching s...

Page 17: ...n RMS in mm s n Peak to peak in mm s n RMS in g n Peak to peak in g The values are determined within set time windows and output cyclically The maximum value since the power supply was switched on can...

Page 18: ...f the machine supports into rigid and flexible systems is due to the relationship of the natural frequency of the overall machine and support system as well as the excitation frequency If the lowest n...

Page 19: ...parameter manual The Turck Vibration Monitor is also available for visualizing process data Access to the sensor parameters and the Turck Vibration Monitor requires the connection of a Turck IO Link...

Page 20: ...bar of a local web browser default http 192 168 1 254 A login is required on the IO Link master in order to edit the settings via the web server and to call the Turck Vibration Monitor Enter the passw...

Page 21: ...V01 01 2022 03 21 Load the device specific IODD into the web server via Load IODD Fig 10 Loading the IODD...

Page 22: ...The process data is recorded over time in seconds The recorded process data is used for example to define warnings for the switching outputs or to determine the measurement axis with the largest vibra...

Page 23: ...irst check whether ambient interference is present If there is no ambient interference present check the connections of the device for faults If there are no faults there is a device malfunction In th...

Page 24: ...return acceptance conditions when returning the device to Turck 12 1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclose...

Page 25: ...lity 5 at 79 58 Hz Temperature Temperature measuring range 40 85 C Temperature linearity deviation 1 Temperature repeatability 2 4 Electrical data Operating voltage 18 30 VDC Ripple 10 Uss Insulation...

Page 26: ...QR20 IOLX3 0 3 RS4 Ambient conditions Ambient temperature 40 85 C Temperature changes EN 60068 2 14 40 85 C Vibration resistance EN 60068 2 6 20 g 5 h axis 3 axes Shock resistance EN 60068 2 27 200 g...

Page 27: ...MARNE LA VALLEE Cedex 4 www turckbanner fr Great Britain TURCK BANNER LIMITED Blenheim House Hurricane Way GB SS11 8YT Wickford Essex www turckbanner co uk India TURCK India Automation Pvt Ltd 401 40...

Page 28: ...RCK RUS OOO 2 nd Pryadilnaya Street 1 105037 Moscow www turck ru Sweden Turck Sweden Office Fabriksstr ket 9 433 76 Jonsered www turck se Singapore TURCK BANNER Singapore Pte Ltd 25 International Busi...

Page 29: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100031992 2022 03 100031992...

Reviews: