V01.01 | 2022/03
19
9.2
Setting via FDT/IODD
The devices can be set via a PC with an FDT frame application (e.g. PACTware). All the required
Turck software components can be downloaded via the Turck Software Manager:
n
PACTware
n
IODD
n
DTM for USB-2-IOL-002 IO-Link adapter
n
IODD DTM Configurator
The Turck Software Manager can be downloaded free of charge from
The USB-2-IOL-002 USB IO-Link adapter (ID 6825482) is required for connecting to the PC.
A 4-pin standard sensor cable (e.g. RKC4.4T-2- RSC4.4T/TXL; ID 6625608) is required for
connecting the sensor to the USB-2-IOL-002 IO IOL-Link adapter.
Further information on setting the devices via IODD with a configuration tool is provided in the
IO-Link commissioning manual.
9.3
Setting and visualization with the Turck Vibration Monitor
The device can be configured and tested via a Turck IO-Link master (e.g. TBEN-S2-4IOL). The
integrated web server of the IO-Link master offers access to all the parameters of the sensor
IODD. An overview of the IO-Link parameters as well as descriptions are provided in the IO-Link
parameter manual. The Turck Vibration Monitor is also available for visualizing process data.
Access to the sensor parameters and the Turck Vibration Monitor requires the connection of a
Turck IO-Link master. The following table shows the firmware version of the IO-Link masters
required for using the Turck Vibration Monitor:
IO-Link master
Firmware version
FEN20-4IOL
V1.2.0.0
TBEN-L4-8IOL
V3.3.2.0
TBEN-L5-8IOL
V3.3.2.0
TBEN-LL-8IOL
V1.1.1.0
TBEN-S2-4IOL
V3.4.1.0
Refer to the instructions for use of the relevant device for information on the Turck IO-Link
masters.
Connect the IO-Link master to the power supply.
Connect the IO-Link master to a PC via the Ethernet interface.
Connect the CMVT… to an IO-Link port of the IO-Link master.
If no IO-Link master is available with the appropriate firmware version, the CMVT… can be set
via the web demo and configuration tool. This requires the use of an IO-Link adapter (e.g.
USB-2-IOL-0002; ID 6825482) for the connection between the PC and the sensor. The above-
mentioned FEN20-4IOL and TBEN… IO-Link masters can also be used with older firmware ver-
sions. The web demo and configuration tool enable access to the sensor via the local web
browser.
The web demo and configuration tool can be downloaded free of charge from