13
V01.0| 2016/04
Pro
g
ramm
able Ga
teway
s B
Lxx
-PG-EN-V
3
3.4
Technical data
3.4.1
BL20-PG-EN-V3
Power supply
Power supply
24 VDC
System supply
24 VDC/5 VDC
Field supply
24 VDC
Permissible range
18...30 VDC
Nominal voltage from module bus
200 mA
Nominal current from module bus
8 A
Max. system supply current
1.3 A
Connection technology
screw terminals
Field bus
Transmission rate
10/100 Mbps, Full/Half Duplex, Auto Negotiation,
Auto Crossing
Address assignment
Rotary coding switches, PGM, DHCP
Connection technology
RJ45-connector
PLC data
Programming
CODESYS 3
Released for CODESYS version
from V 3.5.6.30
Programming
IEC 61131-3 (IL, LD, FBD, SFC, ST)
OPC
yes
OPC UA
no
Application tasks
5
Programming interface
Ethernet, USB
Processor
ARM, 32 Bit
Cycle time
< 1ms for 1000 IL- commands (without I/O cycle)
Real time clock (RTC)
yes
Program memory
1024 kByte
Data memory
512 kByte
Input data
4 kByte
Output data
4 kByte
Non-volatile memory
16 kByte
Web server
Default IP address
192.168.1.254
Service interface