
15
V01.00 | 2020/04
Rotary switches:
The function on/off delay is not part of the safety function and must be set to 0 s.
[A1D] switching point: G = (M1 * 100 + M2 * 10 + M3 * 1) * 10
E
Hz
Example 1: 321 mHz: M1 = 3, M2 = 2, M1 = 1; E = -3
Example 2: 50.6 kHz: M1 = 5, M2 = 0, M1 = 6; E = 2
Hysteresis: H = {0.5, 1.0, 2.5, 5.0, 7.5, 10.0, 12.5, 15.0, 17.5, 20.0} [%]
Switching mode
Selection
Description
2-point
In 2-point mode a lower switch point BotOff and an upper switch point TopOn can be defined in
the permissible measuring range.
The switch points must fulfill the following condition:
BotOff ≤ TopOn
The hysteresis can be 0.
The switching behavior depends on parameter “inversion”.
The following figure shows the switching behavior when inversion is deactivated:
Fig. 4: 2-point mode
4-point
In 4-point mode a window with a lower and upper hysteresis is formed.
The switch points must fulfill the following condition:
BotOff ≤ BotOn < TopOn ≤ TopOff
The hysteresis can be 0.
The switching behavior depends on parameter “inversion”.
The following figure shows the switching behavior when inversion is deactivated:
Fig. 5: 4-point mode
S1
S8
[E
1
] F
max
[kHz]
0.1
0.2
0
.
1
5
.
0
1.5
2
5
10 15
20
0
1
-3 -2
-1
E
2
3
0
1
4
5
6
7 8
9
M3
2
3
0
1
4
5
6
7 8
9
M2
2
3
0
1
2
4
3
5
6
7 8
9
M1
[A
1
D] switching point
Hysteresis [%]
0.5
1.0
0
.
5
5
.
2
7.5
10
12.5
15.0 17.5
20
[A
1
D] SUD [s]
OFF
0.1
1
5
.
0
5
10
30
60 90
120
[A
1
D] ON / OFF delay [s]
0/0
0.5/0
0.75/0
1.0/0
0/0.5
0/0.75
0/1
0.5/0.5 0.75/0.75
1/1
Config
BotOff TopOn
f [Hz]
de-energized
energized
Relay
BotOff BotOn
TopOn TopOff
f [Hz]
de-energized
de-energized
energized
Relay