U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
M a s t e r E c o N e t P l u s E C + + L S R S 4 8 5
I n M n 1 8 E P E
e n R e v . 0 0
T U R B O S r l
D u s t F i l t e r C o m p o n e n t s
V i a P o 3 3 / 3 5 2 0 8 1 1 C e s a n o M a d e r n o ( M B ) I t a l y T e l + + 3 9 0 3 6 2 5 7 4 0 2 4 F a x + + 3 9 0 3 6 2 5 7 4 0 9 2
2 5
Default Settings
B a s i c S e t t i n g
P a r a m e t e r
S e t t i n g V a l u e
Operating Mode
Automatico
Valve Pulse Time
200 m. seconds
00200
Valves Pause Time
20 seconds
00020
Valves Number
1
00001
Units of Measure
kPa
Start Of Cleaning dP
0.80 kPa
00800
Stop Of Cleaning dP
0.40 kPa
00400
A d v a n c e d S e t t i n g
P a r a m e t e r
S e t t i n g V a l u e
dP Fan Recognition
0.10 kPa
00100
Cleaning Cycles Fan Off
2
00002
Time Impulse Valve
200 m. seconds
00200
Time Valve Pause
20 seconds
00020
Precoating
Disabled
Precoating Start dP
1.50 kPa
01500
Cycles Special Manual Mode
2
00002
Pause Special Manual Mode
200 m. seconds
00200
A l a r m s
P a r a m e t e r
S e t t i n g V a l u e
dP Dirty Filter
3 kPa
03000
Enable Minimum dP
Disabled
Threshold dP Minimum Alarm
0.20 kPa
00200
Hours Counter For Fan
Disabled
Replacement Filters Hours
1000
01000
M o d b u s S e r i a l C o m u n i c a t i o n
P a r a m e t e r
S e t t i n g V a l u e
Address
1
00001
Baud rate
9600
09600
Parity
None
Stop bit
1
00001