D u s t F i l t e r C o m p o n e n t s
V i a P o 3 3 / 3 5 2 0 8 1 1 C e s a n o M a d e r n o ( M B ) I t a l y T e l + + 3 9 0 3 6 2 5 7 4 0 2 4 F a x + + 3 9 0 3 6 2 5 7 4 0 9 2
1 7
Enter the number of working hours desired to trigger
the filtering element replacement alarm
(sleeves/cartridges), the alarm is only generated if
the fan hour meter is enabled and the fan remote
switch connected to terminals 17_18 on connector
P13 on the electronic board.
R e p l ac e F i lt er s (h )
Calibration / Test Menu
Press the
Menu
key in the home page.
Use the arrows
to select Calibration/Test.
Press
OK
Calibration / Test Menu Items
Use the arrows
to select the item to be set.
Keys
to increase/decrease the value or
change an item condition such as Enable / Disable.
Press
exit
to save and exit.
Press the keys
to manually start the
solenoid valves connected to the electronic board in
sequence.
No . V a lv e ( + /- = O N )
Press in sequence the keys
to calibrate
zero dP, press the + hold it down then press the -.
Run this operations with the filter fan off.
Z er o d P =
4 m A O ut pu t
Press the keys
to calibrate the 4mA output
which corresponds to zero dP.