background image

 

 

 

TURBO

 s.r.l. 

Electronic Control Systems For Dust Collectors 

e-mail: [email protected]    web: www.turbocontrols.eu 

TEL. ++39 (0)362 574024    FAX ++39 (0)362 574092

 

 

ECONOMIZER 

E2T 

24Vdc

 

25 ÷ 56 OUTPUTS

 

 

User Manual

 

 

 

 

 

05/01/2016 

Manual Release 1.00 

Hardware Release 1.01

 

Summary of Contents for Economiser E2T

Page 1: ...trol Systems For Dust Collectors e mail info turbocontrols it web www turbocontrols eu TEL 39 0 362 574024 FAX 39 0 362 574092 ECONOMIZER E2T 24Vdc 25 56 OUTPUTS User Manual 05 01 2016 Manual Release...

Page 2: ...ing is performed every 10 seconds the time interval is editable Four operation modes manual automatic automatic with forced cycle proportional Operating times expressed in seconds with selectable rang...

Page 3: ...ntain 2 clean contacts on terminals 4 9 di J4 Maximum permitted load 2A 24Vdc Fuse 1 x 3 A 24Vdc Working Temperature from 10 C to 55 C Storage Temperature 20 C to 60 C Timer Specifications Pulse Time...

Page 4: ...fore opening At the end of the operations close the device to restore the correct degree of protection before powering up Use flame retardant cables with a minimum cross section area of 0 75mm to conn...

Page 5: ...The OK button is used to confirm data and reset alarms If the button is pressed during ordinary operation the activity hour meter is displayed The Button pressed during the ordinary operation displays...

Page 6: ...vation Possible values 1 number of outputs set in F04 Press SET to activate the set output F07 Zero dP threshold Possible values 0 00 kPa 3 99 kPa step 0 01 Default 0 00 kPa F08 Cleaning cycle start t...

Page 7: ...00 kPa 3 99 kPa step 0 01 Default 2 00 kPa F20 Enabling Minimum dP Alarm function Possible values 0 disabled 1 enabled Default 0 disabled F21 Min dP Alarm Threshold Broken Sleeve Cartridge Possible va...

Page 8: ...is self reset E07 Solenoid valve current higher than maximum threshold Check correct connection of the solenoid valve and respective data The alarm is self reset E08 Output short circuit The signaling...

Page 9: ...E14 alternates with the indication of the interested output is shown as Uxx where xx is the number of the output and the value of dP An output is considered a short circuit if not responding for 3 fo...

Page 10: ...ill work as a programmable cycle sequencer in manual mode The connected outputs will be activated at the programmable frequencies Manual mode can be activated by accessing the configuration menu and s...

Page 11: ...hen the dP pressure drops under the threshold defined in F12 The pulse time of the valves will always be that defined in F02 while the pause time in this case is defined in F14 The display alternately...

Page 12: ...is not supplied with the control unit A card with a maximum of 32GB can be used The card must be formatted FAT32 which is the format recognized by all devices and operating systems Before removing the...

Page 13: ...12 Connection Diagram...

Page 14: ...d with a jumper on two 12 13 terminals to simulate the state of the plant as if the fan was turned on Alarm Relay K1 4 5 terminals The relay is normally closed opens in case of alarms and opens to the...

Page 15: ...14 Connection Diagram Expansions Expansion Up To 32 Channels Expansion Up To 40 Channels...

Page 16: ...15 Expansion Up To 48 Channels...

Page 17: ...16 Expansion Up To 56 Channels...

Page 18: ...lenoid valve common 53 Solenoid output 23 31 Solenoid output 01 54 Solenoid output 24 32 Solenoid output 02 33 Solenoid output 03 04 Alarm relay contact 01 34 Solenoid output 04 05 Alarm relay contact...

Page 19: ...30 76 Solenoid output 46 61 Solenoid output 31 77 Solenoid output 47 62 Solenoid output 32 78 Solenoid output 48 Expansion up to 40 channels Expansion up to 56 channels Terminal Description Terminal D...

Page 20: ...19 Installation And Casing Dimensions...

Page 21: ...from contact 1 from dP 1 F12 Fan dP threshold if F11 1 If fan off 0 10 kPa F13 Number of cycles after fan stop 1 F14 Pause time between solenoid valves in cycle with fan off 010 F15 Maintenance freque...

Page 22: ...ronic component deemed defective exclusively at our workshop except in the presence of contrary agreements to be authorized by the company Exclusions From Warranty The warranty is void in the case of...

Page 23: ...MANUAL mode F01 0 Do alarm messages appear Check the alarm code with the table Do the alarms fail to activate signalling devices System wiring errors No power to alarm devices The alarm devices must b...

Page 24: ...Complies with the following directives Machinery Directive 2006 42 EC Electromagnetic compatibility compliant with Harmonised European standards EN61000 6 2 2005 class B of EN61000 6 4 2001 Low Voltag...