Modbus RTU protocol & registers
Modbus message
Following the ModBus protocol standard requirements, it is possible to write and read the E9T control unit
registers in order to configure parameters, perform functions and check the device status in real-time operations.
Standard Modbus message for the E9T devices
Device Address
Comprises between 1 and 127
. The “0” value is not permitted.
Func ID
Func 03 (Read Holding registers)
Func 06 (Write Single register)
Data
The E9T register (AND value if writing a register) ;
CRC
The cyclic redundancy check is calculated following CRC16 algorithm criteria.
E9T Modbus registers
The complete list of E9T Modbus registers is listed below. In the access column R means that the related register
are read-only and R/W means that the related register can be read and also written.
DEVICE Settings
Item
Register
Access
Default
Note
Device software version
0x0000
R
Software release mounted
Device hardware version
0x0001
R
Hardware version of E9T
Alarm RESET
0x0002
R/W
0
1= force alarm RESET
Buzzer RESET
0x0003
R/W
0
1= force buzzer RESET
Device serial No.
0x000C
R/W
0
Serial number
Device menu language
0X000E
R/W
0
0=ITA, 1=ENG, 2=FR, 3=DE, 4=ESP
Enable/Disable local GUI
0X000F
R/W
0
0=Enabled 1=Disabled
Device ModBus address
0X0060
R/W
1
1÷127
Device Communication speed
0X0061
R/W
2
0=38400 Baud
1=19200 Baud
2= 9600 Baud
Device Communication Parity bit
0X0062
R/W
0
0=No Parity
1=Odd Parity
2=Even Parity
Device Communication Stop bit
0X0063
R/W
1
0=2 Stop bit 1=1 Stop bit
TRIBO Alarms Settings
Item
Register
Access
Default
Note
Pre-Alarm threshold
0x0010
R/W
800
x 0,01 mg/m
3
Pre-Alarm Time
0x0011
R/W
300
x 0,5 seconds
Alarm threshold
0x0012
R/W
1500
x 0,01 mg/m
3
Alarm Time
0x0013
R/W
60
x 0,5 seconds
Peak threshold
0x0014
R/W
3000
x 0,01 mg/m
3
Peak Time
0x0015
R/W
10
x 0,5sec