The E9T control unit is provided of on-
board 220Ω
termination line resistor for RS-485 Bus.
When JP11 jumper (red highlighted) is :
Open : Termination line resistor disconnected
Closed: Termination line resistor connected
Suggested RS-485 cable
Manufacturer
: Belden
Application
: Industrial
Product code
: 3106A
Poles
: Twisted pair + single pole
Shielded
: YES
Type
: UV resistant
The Ground Terminal
E9T control unit have a GND (ground) terminal in order to provide a stable voltage reference for RS-485 shielded
cable. If a shielded cable is used for RS-485 connection it must be connected only in one side.
Do not connect the GND terminal to an external device ground !
Modbus communication settings
E9T control unit is provided of a dedicated menu accessible by the local user interface useful to configure the
Modbus communication parameters:
Ref
Item
Parameter
Measure
Unit
Factory
default
Range
M6.1
Address
Set the RS-485 address of the Control Unit
on the network
Address
1
1
255
M6.2
Communication speed
Set the speed of the communication
Baud rate
Baud
9600
9600
38400
M6.3
Parity
Set the parity mode of the byte
Parity
Bit
None
None
Even
M6.4
Stop
Set the number of Stop bits
Stop bit
Bit
1
1
2