Turbo Air ADR043AE Installation & Operation Manual Download Page 12

 

12

than  compressor  power  by  fan  delay 

thermostat. If it does not, a partial defrost 

results  and  the  residual  water  and  slush 

will  re-freeze  into  ice  during  the  next 

cycle.  Ice  removal  will  require  a  manual 

defrost. 

 

Defrost Thermostat 
 
Bimetal Disc Type 

Turbo  air  uses  Klixon  type  thermostat 

made by Texas Instruments Company. 

This  thermostat  terminates  defrost  at 

50℉(10℃)  and  prevents  the  fans  from 

running  when  the  coil  temperature  is 

above 

40℉(4.4℃). 

And 

defrost 

termination/fan 

delay 

thermostat 

terminates  defrost  at  55℉(12.8℃)  after 

defrost is finished.   

This  will  allow  fan  delay  time  for 

eliminating  the  residual  water  and  slush 

in the evaporator coil. 

Fan  delay  time  can  be  eliminated  by 

jumping the fan switch contacts. This will 

allow  the  fans  to  start  immediately  after 

defrost  termination.  This  will  disable  the 

fan delay. 

When  the  coil  temperature  reaches 

approximately  40℉(1.7℃),  fan  delay  is 

sends  a  signal  to  the  control  circuit,  and 

it  will  run  fan  motor.  If  you  wish  to 

control fan delay time and defrost   

termination  time,  adjust  the  position  of 

thermostat.  If  this  method  is  used,  it  will 

result in higher temperature. 

 

Adjustable Type ( F25 Series ) 

The  F25  Control  terminates  defrost  and 

delays evaporator fan operation following 

a  defrost  cycle.  The  coil  temperature 

rises  during  the  defrost  cycle  to  the 

control cut-out setting. At this setting the 

defrost cycle terminates and refrigeration 

starts.  The  fan  remains  off  during  the 

initial  start-up  of  the  refrigeration  cycle. 

When  the  coil  temperature  drops  to  the 

control  cut-in  setting,  the  fan  is  turned 

on.  The  delayed  fan  operation  prevents 

warm moist air from being circulated into 

the  controlled  space  and  danger  of 

increased  vapor  pressure  and  product 

damage is eliminated. 

 

Defrost Timer Setting 

 

For Paragon’s    8145-20B type ; 

Timer should be set correctly. Determine 

the  number  of  defrosts  per  day  and  the 

best  time  of  day  for  it  to  occur.  Insert 

pins accordingly. Set the fail-safe time to 

terminate  the  defrost  a  few  minutes 

beyond 

the 

estimated 

temperature 

termination  time.  Air  defrost  termination 

time  is  usually  30  to  50  minutes.  The 

colder  the  room,  the  longer  the  fail-safe 

time  required.  Electric  defrost  systems 

normally have a 25 to 40 minute fail-safe 

time. 

 

Summary of Contents for ADR043AE

Page 1: ...ce of Innovation Part No KUCTB2504 September 2020 edition Refrigeration System Installation Operation Manual Please read this manual completely before attempting to install or operate this equipment U...

Page 2: ...Inspection 3 Locating Unit Cooler 4 Unit Cooler Piping 6 Expansion Valve Selection 8 Defrost 11 Locating and Mounting Condensing Unit 14 System Operation 16 Unit Cooler Troubleshooting 19 System Trou...

Page 3: ...o prevent electric shock Please call the specialized installation company or trained personnel when you installing moving operating of the unit Field wiring must confirm to the requirements of units e...

Page 4: ...ded location methods of Unit Cooler 1 Avoid placing Unit Cooler close to doors Install like Figure 3 or Figure 4 2 Avoid having them face each other when installing multiple units Install like Figure...

Page 5: ...rea above the unit cooler must be sealed or exposed in such away to allow hand cleaning without the use of tools When lagging or bolting unit flush to the ceilings seal the joint between the top and t...

Page 6: ...ing installation of the piping to prevent entrance of foreign matter Use only refrigeration grade copper tubing properly sealed against contamination Figure 8 Suction piping installation on an evapora...

Page 7: ...gh walls or ceilings Precautions should be taken to see that the piping does not touch any structural the transmission of vibration into the building The piping chase must be thoroughly sealed to prot...

Page 8: ...SBFDE A C ADR171AE 17213 SBFSE B C SBFDE A C ADR191AE 19213 SBFSE B C SBFDE A C ADR258AE 25883 SBFSE B C SBFDE B C ADR325AE 32584 SBFSE C C SBFDE B C ADR352AE 35287 SBFSE C C SBFDE B C ADR392AE 39317...

Page 9: ...56BE 15793 SBFSE B Z SBFDE A Z TCE175BE 17697 SBFSE B Z SBFDE A Z TCE214BE 21415 SBFSE C Z SBFDE B Z TCE241BE 24247 SBFSE C Z SBFDE B Z TCE288BE 28959 SBFSE C Z SBFDE C Z TCE325BE 32738 SBFSE C Z SBFD...

Page 10: ...00 150 30 75 100 150 30 75 100 150 30 75 100 150 3000 1 2 5 8 5 8 5 8 1 2 5 8 5 8 7 8 5 8 5 8 7 8 7 8 3 8 3 8 3 8 3 8 4000 1 2 5 8 5 8 5 8 5 8 5 8 7 8 7 8 5 8 5 8 7 8 7 8 3 8 3 8 3 8 3 8 6000 5 8 7 8...

Page 11: ...r may be adequate to keep the evaporator coil clear of frost In other applications a defrost timer may be necessary to help assure a clear coil in a medium temperature environment Air defrost is initi...

Page 12: ...mination time adjust the position of thermostat If this method is used it will result in higher temperature Adjustable Type F25 Series The F25 Control terminates defrost and delays evaporator fan oper...

Page 13: ...ntacts between terminals 2 and 4 are normally closed when timer is energized and open during a defrost to de energize refrigeration and fans Setting Defrost Initiation Time Move a white tab tripper on...

Page 14: ...saves energy in low ambient conditions Fan speed controller keeps the condensing pressure at a steady level by regulating the speed of the AC EC fan motors When pressure is declining the controller d...

Page 15: ...ts Spring Mounted Compressor Semi hermetic compressor unit use the mounting assembly shown in Figure 11 the shipping spacer is to be in place during shipment to insure maximum support for the compress...

Page 16: ...djusting the expansion valve Evaporator superheat greater than 14 can substantially reduce system capacity while superheat less than 4 has the potential for flood back Compressor Superheat Compressor...

Page 17: ...ne in the high side only and with liquid metering devices If R 404A is used liquid must be charged and read up refrigerant explanatory Start up Use the following operating procedure after the installa...

Page 18: ...on the high pressure side it is necessary to check the system so be sure to reset the system after visiting the site Turbo air applied a manual reset method to protect the system Refer to the followin...

Page 19: ...Ice build up in coil quickly Fin spaced too narrow Replace coil Evaporating temperature too low Adjust expansion valve Decrease of air volume Check fan and clean air filter Unit cooler capacity is too...

Page 20: ...cle too short Adjust defrost thermostat or timer for longer cycle Defective timer or defrost thermostat Replace defective component Ice accumulating on ceiling around evaporator on fan guard or blades...

Page 21: ...ne solenoid not open Repair or replace coil Noisy Compressor Flooding of liquid refrigerant into crankcase Check expansion valve setting Improper piping support on suction or liquid line Relocate add...

Page 22: ...itions are within allowable limits Discharge valve partially closed Open valve Dirty condenser coil Clean coil Overcharged refrigerant Reduce charge Compressor loses oil Lack of refrigerant Check for...

Page 23: ...23 Field Wiring Diagram 1 Typical wiring diagram for single evaporator with or without defrost timer...

Page 24: ...24 Diagram 2 Typical diagram for single evaporator defrost timer only Diagram 3 Typical diagram for single evaporator with defrost timer and single phase heater contactor...

Page 25: ...25 Diagram 4 Typical diagram for single evaporator with defrost timer and 3 phase heater contactor Diagram 5 Typical diagram for single evaporator defrost timer only TTE TYPE...

Page 26: ...26 4184E Conant street Long Beach CA 90808 FAX 310 900 1008 Toll Free 888 900 1002 U S A Canada http www turboairinc net...

Reviews: