WALK-TEST
SENSOR
The final step for any sensor installation is a walk-test. This will help to ensure the unit is functioning correctly and is
capable of detecting pedestrian traffic as intended. Refer to the current ANSI A156.10 or A156.19 Standard, Section 8,
for proper performance guidelines.
1.
Increase or decrease the sensitivity potentiometer as necessary to achieve the desired detection field. The
potentiometer,under normal operation, directly adjusts the sensitivity of the detection field.
2.
The red LED (2) will illuminate when detection occurs. If the LED comes on as the door is closing, the detection field
may be too close to the door and/or sensitivity may be too high. Adjust as necessary, and walk-test again.
WALK-TEST
SENSOR
ü
WEATHER COVER - P/N 200.1069
The weather cover
(ERA) guards the sensor from rain, snow, etc. There are no tools needed for installation
and can be used in conjunction with a ceiling mount.