920.1004.02
10
ADDITIONAL FUNCTION
SETTINGS
These additional settings can be adjusted by enabling the potentiometer to affect different functions through the dip
switch arrangements. The adjustable settings are for hold time and default setting restoration. Every adjustment with
the potentiometer starts the same way, dip switch 5 ON, and ends the same way, dip switch 5 OFF.
The additional functions must be accessed during the first 10 seconds of powering ON and is signified by
a flashing / green LED pattern.
MANUAL RELAY
HOLD TIME ADJUSTMENT
1.
Turn dip switch number 6 to ON.
2.
Turn dip switch number 5 to ON (Right LED will flash).
3.
Turn dip switch number 1 to ON (Red and green LED will flash simultaneously).
4.
Turn potentiometer to the far left, then to desired position.
5.
Turn DIP switch 1 back to OFF to store change (Green LED flashes).
6.
Turn DIP switch 5 back to OFF.
7.
Now that hold time is stored, turn potentiometer back to desired detection sensitivity.
NOTE:
LEDs will flash and click according to time increments.
RESTORE DEFAULTS
&
CLEAR MEMORY
1.
Turn dip switch #5 ON and verify green LED is flashing.
2.
Then turn dip switch #4 ON and verify red LED flashes.
3.
Then turn dip switch #4 OFF. Sensor is re-started.
4.
Turn dip switch #5 OFF after sensor reinitializes.