PCM30U, PCM30U-OCH – User's, Operating and Maintenance Manual
E.2.2
Technical parameters
Two-way transmission of analogue signal at a frequency of f = 50 Hz of two linksof
comparison protections of the DLN910, S103B, S105 type
Compartive
protections – setting
A
(P
OUT
max: 2x5 VA)
One-way transmission of two routes of the 50Hz synchronisation signal with a constant
voltage amplitude and exact phase for synchronisation of the power plant units with the
frequency and phase of the region (substation)
Synchronizing of
generators – setting
B
(P
OUT
max: 2x5 VA)
One-way transmission of one link of the 50Hz synchronisation signal with a constant
voltage amplitude and exact phase for synchronisation of the power plant units with the
frequency and phase of the region (substation) with parallel connection of both power
amplifiers for the doubling of the maximum output power of one channel from 5 VA to
10VA, at an OUT max of 100 V AC
Synch. of generators
– dobled amplifier
Setting C
(P
OUT
max: 1x10 VA)
Maximum input voltage of the signal 50Hz (setting A, B, C)
70 or 110 V AC
2 k
Ω
or 5 k
Ω
: setting A)
50 or 100 V AC
2 k
Ω
or 5 k
Ω
: setting B)
100 V AC (5 VA)
Maximum output voltage, 50Hz, up to a load of:
1 k
Ω
(doubl. ampl. setting C)
100 V AC (10 VA)
Phase stability of the output voltage, better than
2.5
°
/ Hz
Amplitude stability of the output voltage
± 3 V AC
Amplitude distortion at output level decreased by 20 dB
<
1 dB
Harmonic distortion of the output voltagte
<
5%
Crosstalk ratio between adjacent subchannels
>
60 dB
Signal to noise ratio (to rated output level in idle channel)
>
60 dB
high
>
50 k
Ω
medium – (for DLN910)
5 k
Ω
± 10%
Input impedance options for the 50Hz signal
low – for S103B, S105)
2 k
Ω
± 10%
Time of 50Hz signal transmission without additional setting of delay
about 0.3 ms
Delay setting in each channel’s transmitting direction, using dig. delay switch at the
unit’s panel, in jumps of
Δ
t = 0.5 ms within the range of:
0 ms – 23.5 ms
Setting the delay/phase lead (function is continuously adjustable with jumpers on the
unit), using an analogue correction phase link (continuously adjustable by the
resistance trimmer on the unit’s panel) in each channel’s transmitting direction, within
the range of:
0.05 ms to
± 0.5 ms
0.4 ms to
± 5 ms
Maximum cross section of external cable conductors connected to the terminal blocks
2 mm
2
Mechanical break/make contact of the error relay (with jumper-adjustable function of the
“break” or “make” contact), supplied with direct current from a DC voltage source
located in the control centre room, its maximum contact current level being indirectly
proportional to the given voltage level
0.4 A / 250 V DC to
5 A / 24 V DC
Electrical strength of the input and outpt terminals of the analogue signal and the
electrical strength of the fault signalling terminals
2 kV / 1 min AC
Resistance of the input and output terminals of the analogue signal against overvoltage
wave whose shape is described in the EN 334000 Standard – 10 ms / 700 ms
5 kV DC
Resistance of the fault signalling terminals against overvoltage wave as referred to above
1 kV DC
Power Channel Modules
E-32
446S037.914.14N00