- 14 -
Direct voltage is low (6
~
9V).
N.G.
O.K.
Step1
AVR unit
AVR unit
Recheck
O.K.
Check
Exchange
O.K.
N.G.
Go Step2
N.G.
OK
Step2
Bridge diode
Bridge diode
Recheck
O.K.
Check
Exchange
O.K.
NG
Go Step3
N.G.
Step3
Stator check
・Resistance of each winding is measured.
It will be stator exchange if there is a defect.
O.K.
Recheck