10
Command list
Setting command
Required setting
command
Specified setting command
Command
Response
Command frame
Response
Setting item, range
Totalizing constant
RC01
20
WC01 99999
99999
20~99999
Instant full scale
RC02
20000
WC02 10000
10000
20~20000
Cut off
RC03
0
WC03 1
1
0~10%
Instantaneous display
cycle
RC06
1
WC06 1
1
0(100ms), 1(1s), 2(5s)
Totalized decimal
point
RC07
2
WC07 1
1
0(0), 1(0.0), 2(0.00),
3(0.000),4(0.0000),
5(0.00000)
Instant decimal point
RC08
0
WC08 1
1
0(0), 1(0.0), 2(0.00),
3(0.000),4(0.0000),
5(0.00000)
Initial totalizing value
RC09
0
WC09 999999
999999
0~999999
Display 1 switching
RC10
0
WC10 1
1
0(Inst.), 1(Totalizer)
Display color
RC11
0
WC11 1
1
0(RED), 1(GREEN)
Reset totalizing
function
RC12
0
WC12 1
1
1(ON), 0(OFF)
Synchronized
totalization pulse
division
RC13
0
WC13 1
1
0(1/1), 1(1/10), 2(1/100)
Synchronized
totalization pulse
width
RC14
0
WC14 1
1
0(100ms), 1(50ms),
2(10ms)
Display switch-off
function
RC15
1,99
WC15 1,99
1,99
0(Invalid)/ 1(All display)/
2(Display2), 0~99
Invalid of reset key
RC16
0
WC16 1
1
0 (Invalid), 1(Valid)
Pause/Latch
RC17
0
WC17 1
1
0(PAUSE), 1(LATCH)
Over display of
display 1
RC18
0
WC18 1
1
0(OFF)/1(ON)
AL1 Comparative
value
RC41
999999
WC41 999999
999999
0~999999
AL2 Comparative
value
RC42
999999
WC42 999999
999999
0~999999
AL3 Comparative
value
RC43
999999
WC43 999999
999999
0~999999
AL4 Comparative
value
RC44
999999
WC44 999999
999999
0~999999
Batch switching
RC45
0
WC45 1
1
0(ALARM), 1(BATCH)
AL3 Output width
RC46
0
WC46 1
1
0(0.1s), 1(0.2s), 2(0.5s),
3(1.0s),4(Continuous)
AL4 Output width
RC47
0
WC47 1
1
0(0.1s), 1(0.2s), 2(0.5s),
3(1.0s),4(Continuous)
AL4 Auto reset
RC48
1
WC48 0
0
1(ON), 0(OFF)
Analog output
switching
RC75
0
WC75 0
0
0(Inst.), 1(Totalizer)
Full scale of analog
output
RC79
999999
WC79 999999
999999
200~99999
Key protection
RC00
1
WC00 0
0
1(ON), 0(OFF)