Safety, Installation, and Operations Manual

©2020 TSC PowerHome All rights reserved. Contents subject to change without notice. TSC-MAN-0001 Rev 02, 06-2020 

High Performance Solar

PV output.

 

y

All TSC modules are equipped with connecting cables and locking connectors. Modules have been designed 

to be easily connected. The locking connectors are not to be disconnected under load. The proper procedure 

to disconnect the module locking connectors is as follows: Turn off the inverter(s), shut off the module DC 

disconnect(s) and then disconnect the locking connectors using an approved tool set. To re-install, connect the 

module locking connectors, turn on the module DC disconnect(s) and turn on the inverter(s).

 

y

Match the polarities of the cables and terminals when making connections; failure to do so may result in 

damage to the modules and other electrical equipment.

 

y

A properly rated and certified over-current device must be connected in series with each module or string of 

modules when reverse currents can exceed the value of the maximum protective fused value noted on the 

module label. The rating of the over-current device shall not exceed the value of the maximum protective fuse 

rating specified on the module label.

 

y

All TSC modules are factory supplied with bypass diodes located in the junction box.

 

y

The junction box is not designed or certified to be field accessible or maintainable and should under no 

circumstances be opened. Opening the junction box may void the module warranty.

3.1 Grounding (Grid-tied applications)

 

y

Before installing the solar system, contact local authorities to determine the necessary system hardware 

grounding requirements.

 

y

Module frames should be electrically connected to an earth ground for safety and protection from lightning in 

accordance to applicable federal, state and local electrical codes. 

 

y

When using a mounting system, grounding of modules must be accomplished by the method prescribed by the 

mounting system manufacturer.

 

y

Where common grounding hardware (nuts, bolts, star washers, split-ring lock washers, flat washers and the 

like) are used to attach the solar module to a listed grounding/bonding device, the attachment must be made in 

conformance with the grounding device manufacturer’s instructions.

 

Š

Common hardware items such as nuts, bolts, star washers, lock washers, and the like have not been 

evaluated for electrical conductivity or for use as grounding devices and should be used only for 

maintaining mechanical connections and holding electrical grounding devices in the proper position 

for electrical conductivity. Such devices, where supplied with the module and evaluated through the 

requirements in IEC/UL 61730, may be used for grounding connections in accordance with the instructions 

provided with the module.

 

y

Follow these instructions to ground the module.

 

Š

The module frame has four 4.5 mm grounding holes (‘A’) that are shown on the module drawing. Attach 

a 10 AWG (2.588 mm diameter) bare copper ground conductor to a grounding lay-in lug mounted at one 

of the four grounding holes on the module frame. Use a grounding lug with tin plating and stainless-steel 

hardware (#10-32 hex head screw at 4 mm diameter, flat washers, tooth lock washer and nut).

 

Š

A #10 flat washer must be used between the screw head and the grounding lug to prevent damage to the 

tin plating on the lug. Insert a #10 flat washer between the grounding lug and the module frame. A #10 

tooth lock washer must be inserted between the nut and the module frame to break the anodized layer of 

the frame. This mechanical bond between the tooth lock washer and the frame of the module will ensure a 

Summary of Contents for PowerXT R Series

Page 1: ...stallation and Operations Manual 2020 TSC PowerHome All rights reserved Contents subject to change without notice TSC MAN 0001 Rev 02 06 2020 SAFETY INSTALLATION AND OPERATIONS MANUAL Europe TSC PowerXT R Module ...

Page 2: ...bsite solaria com europe for the latest information For warranty text refer to solaria com additional product information For TSC patent information refer to solaria com patents 2020 TSC Corporation All rights reserved TSC PowerHome B V Barbara Strozzilaan 201 1083HN Amsterdam Netherlands solaria com europe Jürgen Fuhrmann Germany Territory Business Development Manager 49 8061 9389885 49 151 15121...

Page 3: ...to change without notice TSC MAN 0001 Rev 02 06 2020 High Performance Solar Table of Contents 1 0 Introduction 4 2 0 Safety Precautions 4 3 0 Electrical Installation 5 4 0 Module Mounting 7 5 0 Maintenance 11 6 0 Disclaimer of Liability 11 7 0 Electrical Specifications 11 8 0 Mechanical Dimensions 12 ...

Page 4: ...me y Do not artificially expose additional high intensity sunlight directly on the module y Do not disconnect modules while under load y All installations must be performed in compliance with local regional national and international statutory regulations guidelines norms and code requirements y For projects in Canada the installations shall be performed in accordance with CSA C22 1 Safety Standar...

Page 5: ...gurations in the same DC string or inverter y For field connections Solaria recommends that all connecting cables be double insulated flexible copper Cu conductors with a minimum rating of 90 C The cable size should be determined by the applicable codes but is recommended that this be no less than 4mm or 12AWG The connectors must be compatible with the factory installed connectors on Solaria panel...

Page 6: ...ted to an earth ground for safety and protection from lightning in accordance to applicable federal state and local electrical codes y When using a mounting system grounding of modules must be accomplished by the method prescribed by the mounting system manufacturer y Where common grounding hardware nuts bolts star washers split ring lock washers flat washers and the like are used to attach the so...

Page 7: ...modules being mounted in accordance to the requirements described in this section 4 1 Site Considerations TSC modules should be mounted in locations that meet the following requirements y Module should not be mounted in locations where it will be in direct contact with salt water y When choosing a site avoid obstructions that could cast shadows on the modules as much as possible 4 2 Mechanical Ins...

Page 8: ...s of the National Electrical Code ANSI NFPA 70 2014 2017 y Any module without a frame laminate shall not be considered to comply with the requirements of IEC UL 61730 unless the module is mounted with hardware that has been tested and evaluated with the module under this standard or by a field inspection certifying that the installed module complies with the requirements of IEC UL y The module has...

Page 9: ... PV module mountings are available and compatible with PowerXT In the absence of manufacturer s recommendations for clamp size Solaria recommends minimum clamp size of 40mm 1 57 Maximum Allowed Loading TEST LOAD CLAMP AREA A CLAMP AREA B Front Load 5400Pa 2400Pa Rear Load 3600Pa 2400Pa 11in 279mm 11in 279mm 11in 279mm CLAMP AREA B 11in 279mm CLAMP AREA B 6in 152mm CLAMP AREA A 6in 152mm CLAMP AREA...

Page 10: ...AMP AREA A CLAMP AREA B Front Load 5400Pa 2400Pa Rear Load 3600Pa 2400Pa 4 0in 101 6mm CLAMP AREA A 6 0in 152 4mm CLAMP AREA A 12 4in 315 7mm 11 4in 290 0mm 11 0in 279 4mm CLAMP AREA B 11 0in 279 4mm CLAMP AREA B 11 4in 290 0mm 6 0in 152 4mm CLAMP AREA A 6 0in 152 4mm CLAMP AREA A 11 4in 290 0mm POWERXT XXXR PMX CLAMP AREAS REVISIONS ZONE REV DESCRIPTION DATE APPROVED D C B A 5 4 3 2 1 E F REV D P...

Page 11: ...8 inches and maximum cantilever of 17 inches Follow racking system manufacturer s recommendations for coupling clamps at the module corners torques and bonding methods For rail less systems maximum allowed loading is 2400Pa front and 2400Pa rear 4 3 Module Direction and Tilt Angle y Modules produce maximum energy when they are pointed directly to the Sun Modules get maximum sunlight throughout the...

Page 12: ...allation operation use and maintenance of the module are beyond TSC s control TSC does not assume responsibility and expressly disclaims liability for loss damage injury or expense arising out of or in any connection with such installation operation use or maintenance of the module y TSC assumes no responsibility for any infringement of patents or other rights of third parties that may result from...

Page 13: ...to change without notice TSC MAN 0001 Rev 02 06 2020 High Performance Solar TSC PowerXT xxxR PD y Nominal dimensions in millimeters and inches Not Drawn to Scale y 4x 4 5mm 0 18in Grounding Holes A y 4x 7 0mm 0 28in x 10 0mm 0 39in Mounting Slots B y Module Weight 21 kg 46 lbs 8 0 Mechanical Dimensions ...

Page 14: ...RT OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF SOLARIA CORPORATION IS PROHIBITED NOTES THE TOLERANCES AND DIMENSIONS ON THIS PAGE ARE FOR THE REFERENCE OF THE INSTALLER FOR MANUFACTURING INFORMATION REFER TO MANUFACTURING DRAWINGS y Nominal dimensions in millimeters and inches Not Drawn to Scale y 4x 4 5mm 0 18in Grounding Holes A y 4x 7 0mm 0 28in x 10 0mm 0 39in Mounting Slots B y Module Wei...

Page 15: ...n and Operations Manual 2020 TSC PowerHome All rights reserved Contents subject to change without notice TSC MAN 0001 Rev 02 06 2020 TSC PowerHome B V Barbara Strozzilaan 201 1083HN Amsterdam Netherlands solaria com europe ...

Reviews: