background image

TROUBLESHOOTING

PROBLEM

The compressor is not working.

The motor buzzes but is not running or 

runs slowly.

The fuses blow

The circuit breaker is repeatedly 

activated.

CAUTION! NEVER USE AN EXTENSION 

CABLE WITH THIS UNIT!

The thermal overload protection 

repeatedly causes interruptions.

Pressure in the tank drops when the 

compressor stops.

Excessive humidity in the discharging 

air.

The compressor operates continuously.

The compressor vibrates.

Air output less than normal.

POSSIBLE CAUSE

1. No electricity.

2. Blown fuse in the installation.

3. Air check is open.

4. Thermal switch is activated.

5. Faulty Pressurestat.

1.  Voltage drop.

2.  Motor winding has a short or is 

open.

3. Faulty check valve or pressurestat.

4. Compressed air in the cylinder.

1.  Wrong fuse capacity.

2. Faulty check valve or pressurestat.

1.  Voltage drop.

2.  Blocked air filter.

3.  There is no adequate ventilation.  

Room temperature is too high.

1.  Loose connections (couplings, 

pipeline, etc.)

2.  Purge key is open.

3. Leaks in the check valve

1. Too much water in the tank.

2. High humidity

3. Admission filter is covered.

1. Faulty pressurestat.

2.  Excessive use of air

1. Loose mounting bolts

2. The tank rubber supports are missing 

or worn.

1. Open the purge key

2. Dirty admission filter.

3. There is a leak in the connection

SOLUTION

1. Is it connected? Check fuse-circuit 

breaker.

2. Replace blown fuse.

3. Restart and determine what caused the 

problem.

4. Push the thermal button to restart.

5. Contact a Truper Authorized Service 

Center.

1. Check with voltmeter. Minimum 

voltage: 115 V˜

2. Contact a Truper Authorized Service 

Center.

3. Contact a Truper Authorized Service 

Center.

4. Turn the ON / OFF switch into the OFF 

position around 15 seconds.  Then 

turn to the AUTO position. 

1. Verify you are using the right fuse. Use 

a time-delay fuse.  Disconnect other 

units using the same circuit or operate 

the compressor in an independent 

circuit.

2. Contact a Truper Authorized Service 

Center.

1. Check with voltmeter. Minimum 

voltage: 115 V˜

2. Clean the filter (see Maintenance 

section).

3.  Move the compressor to a 

well-ventilated area.

1. Check to detect air leaks. Use sealing 

tape in all the leaking connections.

2. Tighten the purge key

3. Disassemble the unidirectional valve.  

Clean and replace. Danger! DO NOT 

DISASSEMBLE THE CHECK VALVE 

WHEN THERE IS AIR INSIDE THE 

TANK. PURGE THE TANK FIRST.

1. Drain the deposit.

2. Move the compressor to a less humid 

area.  Use a filter in the air pipeline

3. Clean or replace the filter.

1.  Contact a Truper Authorized Service 

Center.

2. The compressor is not big enough to 

satisfy the CFM requirements of the 

pneumatic tool.

1.  Tighten

2.  Replace

1.  Pull the safety valve ring to clean the 

bolckage.

2.  Clean or replace admission filter.

3.  Tighten connections.

4

Summary of Contents for COMP-10L

Page 1: ...digo 19215 NOTA IMPORTANTE Este producto no debe quedar expuesto a goteo o salpicaduras por l quidos Compresor de aire Instructivo Lea este Instructivo por completo antes de usar la herramienta ATENCI...

Page 2: ...na o se cruce cuando est en funcionamiento 12 No extienda su radio de acci n Evite toda postura que cause cansancio Cuide de que su posici n sea segura y de que conserve el equilibrio 13 Mantenga las...

Page 3: ...indicadora ubicada en la parte posterior del compresor Si el nivel de aceite no abarca el punto medio circulo rojo entonces llene el dep sito con INTRODUCCI N Lea este instructivo con atenci n antes d...

Page 4: ...t body use eye protection compressor starts automatically moving parts do not touch keep guards in place compressor does not supply breathable air RISK OF BURSTING Do not adjust regulator to result in...

Page 5: ...determinando porqu ocurri el problema 4 Oprima el bot n del interruptor t rmico para volver a restablecerlo 5 P ngase en contacto con un Centro de Servicio Autorizado Truper 1 Revise con un volt metr...

Page 6: ...NOTAS...

Page 7: ...SUCURSAL GUADALAJARA AV ADOLFO B HORN 6800 COL SANTA CRUZ DEL VALLE C P 45655 TLAJOMULCO DE ZU IGA JAL TEL 01 33 3606 5285 AL 90 MICHOAC N FIX FERRETER AS AV PASEO DE LA REP BLICA 3140 A COL EX HACIEN...

Page 8: ...recomendadas o no se haya operado de acuerdo al instructivo o haya sido alterado o reparado por personal no autorizado por Para hacer v lida la garant a o adquirir piezas y componentes deber presenta...

Page 9: ...P 10L Code 19215 Air compressor Manual IMPORTANT NOTICE This product should not be exposed to liquids dripping or splashing Read the user s manual thoroughly before operating this tool CAUTION ENGLISH...

Page 10: ...ing one hand and enables to use both hands Keep proper footing and balance at all times Do not overreach over or walk across the tool when is running 12 Do not extend your range of action Avoid a stan...

Page 11: ...AL HAZARD OF SEVERE INJURY OR DEATH 1 Do not carry out welding jobs in the compressor air tank An extremely dangerous condition may be created If carrying out any welding job on the tank the warranty...

Page 12: ...essure greater than marked maximum pressure of attachment if a regulator has not been installed use only attachment rated at 1 379 kPa 200 PSI or higher do not weld on or repair tank replace DISCONNEC...

Page 13: ...e connection SOLUTION 1 Is it connected Check fuse circuit breaker 2 Replace blown fuse 3 Restart and determine what caused the problem 4 Push the thermal button to restart 5 Contact a Truper Authoriz...

Page 14: ...NOTES...

Page 15: ...GUADALAJARA AV ADOLFO B HORN 6800 COL SANTA CRUZ DEL VALLE C P 45655 TLAJOMULCO DE ZU IGA JAL TEL 01 33 3606 5285 AL 90 MICHOAC N FIX FERRETER AS AV PASEO DE LA REP BLICA 3140 A COL EX HACIENDA DE LA...

Page 16: ...60 CDMX Mex or at the store where you bought it or at a service center listed in the attached warranty policy and or at www truper com Transportation costs resulting from compliance of this warranty w...

Reviews: