7.7
Actual values
Display actual values
Ø
Display the current values at the mains connection of the
AC-DC module.
−
User interface:
Select >
Operation
>
Device control AC-DC
.
In the "Status AC modules" area, enter the desired mod-
ule under "Slave module selection". Or enter
0
in order
to display the generally applicable or sum values of all
modules (0 is displayed in the case of values that can-
not be summed).
Read the actual values in the "Status AC modules" area.
DC link voltage is displayed under "DC link v"
and "DC link voltage -" in V.
The apparent power output/draw of the individual phases
(L1, L2, L3) are displayed under "Apparent power Lx" in
kVA.
The effective power output/draw of the individual phases
(L1, L2, L3) is displayed under "Real power Lx" in kW.
The voltages of the individual phases (L1, L2, L3) are
displayed under "Grid Vvltage Lx" in V.
The currents of the individual phases (L1, L2, L3) are dis-
played under "Phase curent Lx" in A.
The frequency is displayed under "Grid frequency" in Hz.
The overload capacity of the individual phases (L1, L2,
L3) is displayed under "Overload capacity Lx" in %.
−
Modbus:
Read actual values .
7.8
Process set values
Set process set values
Ø
Set the process set values via the web-based user interface:
(see "Setting process set values (AC settings)", pg. 43)
or
Ø
Set the process set values via Modbus: .
A67-0141-00.BKEN-
001-05
2020-06-10
Operation
61
Display AC values