Conditions
■
Initial commissioning was performed
.
■
AC-DC module is in idling condition ("Activate power stage"
= 0).
To connect and operate the TruConvert AC 3025 in parallel
operation with the public low-voltage grid, the following
points are to be adhered to:
Ø
The applicable legal and official regulations.
Ø
Country-specific grid codes (TAB: technical connection
requirements) of the mains operator.
Ø
The configuration of the grid codes is to be agreed upon,
implemented and documented together with the mains oper-
ator prior to connection.
Ø
TruConvert AC 3025 does not satisfy the country-specific
grid- and system protection requirements.
Ø
During operation, the conditions (grid codes, TAB) on which
the decisions regarding the connection of the generating
system and/or of the accumulator were based may
only
be
changed with the consent of the mains operator.
1. Select >
Operation
>
Grid code settings
.
2. In the "Grid code password and save settings" area, enter
the password.
The country-specific grid code can now be activated and
configured.
3. Select >
Operation
>
Grid code settings
.
4. In the "Grid code password and save settings" area, press
"Save grid code settings" to save the entries and to adopt
them in the system control.
The values adopted in the system are displayed on the right
next to the input fields.
This completes entry of the grid code data; you are logged
out automatically. If further changes need to be made to the
grid codes, please log in again.
38
Installation
2020-06-10
A67-0141-00.BKEN-
001-05
NOTICE
Open the "Grid code
settings" tab to make entries
Adopting grid code settings
in system