True Manufacturing Company TGU-2 Installation Manual Download Page 20

............ www.truemfg.com ............

True Food International Equipment, Inc.

18

18

of minutes. To disable one or more of the 6 scheduled defrosts, assign the value “---” (it is the value after “23.5”). Parameters 

DH1

...

DH6

 are accessible both 

in the setup (see §Configuration Parameters) and by keeping button   pressed for 4 seconds during normal operation.

Synchronised defrost

 

. With 

DI2

=DSY and when more units (models AR2-28x3xxx only) are linked to each other as per Fig. 3, synchronised defrosts of all 

linked controllers will take place. The first controller which will start defrost, will also get all other controllers synchronised.

Manual or remote defrost start.

 If 

DFM

=TIM it’s possible to manually start a defrost, by pressing button   for 4 seconds. If 

DFM

=RTC hold button   down 

for 4 seconds to display 

DH1

, then press button   again for 4 seconds to manually start a defrost. Defrost may be also started remotely, if 

DI2

=RDS, through 

the making of the auxiliary contact DI2.

Defrost type

. Once defrost has started, Compressor and Defrost outputs are controlled according to parameter 

DTY

. If 

FID

=YES, the evaporator fans are 

active during defrost.

Defrost termination

. The actual defrost duration is influenced by a series of parameters.

Time termination

 

T2

=NO and 

T3

 different from 2EU: the evaporator temperature is not monitored and defrost will last as long as time DTO. 

Temperature monitoring of one evaporator

 

T2

=YES and 

T3

 different from 2EU. In this case, if the sensor T2 measures the temperature DLI before the time 

DTO elapses, defrost will be terminated in advance.

Temperature monitoring of two evaporators

 

T2

=YES, 

T3

=2EU, 

OAU

=2EU. This function is for the control of two independent evaporators and it switches 

off the individual heating of the evaporator which gets to temperature 

DLI

 first, waiting for the second evaporator to get to that temperature before the time 

DTO

 elapses.

Resuming thermostatic cycle

. When defrost is over, if 

DRN

 is greater than 0, all outputs will remain off for DRN minutes, in order for the ice to melt completely 

and the resulting water to drain. Moreover, if probe T2 is active (

T2

=YES), the fans will re-start when the evaporator gets to a temperature lower than FDD; 

Vice versa, if probe T2 is not active (

T2

=NO) or after defrost has come to an end, such condition does not occur by end of the time 

FTO

, after 

FTO

 minutes 

have elapsed the fans will be switched on anyway.

Caution: if  

DFM=NON or C-H=HEA all defrost functions are inhibited; if DFT=0, automatic defrost functions are excluded. During a high pressure alarm, defrost 

is suspended. During defrost, high temperature alarm is bypassed.

CONFIGURATION PARAMETERS

To get access to the parameter configuration menu, press button 

 

 +   for 5 seconds.

With button 

 

 or   select the parameter to be modified.

Press button 

 

 to display the value.

By keeping button 

 

 pressed, use button   or   to set the desired value. 

When button 

 

 is released, the newly programmed value is stored and the following parameter is displayed.

To exit from the setup, press button 

 

 or wait for 30 seconds.

PAR

RANGE

DESCRIPTION

SCL

1°C;

2°C;

°F

Readout scale.

1°C (with INP=SN4 only): measuring range  -50/-9.9 … 19.9/80°C

2°C : measuring range   -50 … 120°C

°F : measuring range   -55 … 240°F

Caution: upon changing the SCL value, it is then absolutely necessary to re-configure the parameters relevant to the absolute 

and relative temperatures (SPL, SPH, SP, ALA, AHA, etc..).

SPL

-50..SPH

Minimum limit for SP

 

setting.

SPH

SPL.120°

Maximum limit for SP

 

setting.

SP

SPL... SPH Setpoint (value to be maintained in the room). 

C-H

REF; HEA

Refrigerating (REF) or Heating (HEA) control mode.

HYS

1...10°

OFF/ON thermostat differential.

    

SP

SP+HYS

T[°]

ON

OFF

         

SP

SP-HYS

T[°]

ON

OFF

                                                 

CRT

0...30min

Compressor rest time. The output is switched on again after CRT minutes have elapsed since the previous switchover. We 

recommend to set CRT=03 with HYS<2.0°.

CT1

0...30min

Thermostat output run when probe T1 is faulty. With CT1=0 the output will always remain OFF.

CT2

0...30min

Thermostat output stop when probe T1 is faulty. With CT2=0 and CT1>0

  

the output will always be ON.

Example: 

CT1=4, CT2= 6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6 minutes OFF.

CSD

0..30min

Compressor stop delay after the door has been opened (active only if DS=YES).

DFM

NON;

TIM;

RTC

Defrost start mode

NON

 : defrost function is disabled (the following parameter will be FID).

TIM

 : regular time defrost.

RTC

 : the defrost time is scheduled by parameters DH1, DH2...DH6.

DFT

0...99 hours Time interval among defrosts. When this time has elapsed since the last defrost, a new defrost cycle is started.

DH1

...

DH6

HH.M

Scheduled time for defrost 1 to 6. HH hours from midnight, M tens of minutes. Accepted values go from 00.0 to 23.5. After 

“23.5” the value is “---” that means “skipped defrost”. Example: DH1=8.3 means 8.30 AM.

DLI

-50...120°

Defrost end temperature.

DTO

1...120min

Maximum defrost duration.

DTY

OFF;

ELE;

GAS

Defrost type

OFF

: off cycle defrost (Compressor and Heater OFF).

ELE

: electric defrost (Compressor OFF and Heater ON).

GAS

: hot gas defrost (Compressor and Heater ON).

DPD

0...240sec

Evaporator pump down. At the beginning of defrost, defrost outputs (determined by DTY) are OFF for DPD seconds.

DRN

0...30min

Pause after defrost (evaporator drain down time).

DDM

RT;

LT;

 SP;

 DEF

Defrost display mode. During defrost the display will show:

RT

 : the real temperature;

LT

 : the last temperature before defrost;

SP

 : the current setpoint value;

DEF

 : “dEF”.

Refrigerating control (C-H=REF)

Heating control (C-H=HEA)

DDY

0...60min

Display delay. The display shows the information selected with parameter DDM during defrost and for DDY minutes after 

defrost termination. 

FID

NO/YES

Fans active during defrost.

FDD

-50...120°

Evaporator fan re-start temperature after defrost.

FTO

0...120min

Maximum evaporator fan stop after defrost.

FCM

NON; 

TMP; 

TIM

Fan mode during thermostatic control.

NON

 : The fans remain ON all the time; 

TMP

 : Temperature-based control. The fans are ON when the 

compressor is ON. When the compressor is turned OFF, the fans 

remain ON as long as the temperature difference Te-Ta is greater 

than FDT. The fans are turned ON again with FDH differential. 

(Te = Evaporator temperature, Ta = Air temperature);

TIM

 : Timed-based control. The fans are ON when the compressor 

is ON. When the compressor is OFF, the fans switch ON and 

OFF according to parameteres FT1, FT2, FT3

 

(See Fig.2).

FDT

-120...0°

Evaporator-Air temperature difference for the fans to turn OFF after the compressor has stopped.

FDH

1...120°

Temperature differential for fan re-start.

Example

: FDT

 

= -1, FDH=3. In this case, after the compressor has stopped, the fans are OFF when Te > Ta - 1 (FDT), 

whereas the fans are ON when Te < Ta - 4 (FDT-FDH).

FT1

0...180sec

Fan stop delay after compressor stop. See Fig. 2

FT2

0...30min

Timed fan stop. With FT2=0 the fans remain on all the time.

FT3

0...30min

Timed fan run. With FT3=0, and FT2 > 0, the fans remain off all the time.

ATM

NON;

ABS;

REL

Alarm threshold management.

NON 

: all temperature alarms are inhibited (

the following parameter will be 

ADO

).

ABS 

: the values programmed in ALA

 

and

 

AHA represent the real alarm thresholds.

REL 

: the values programmed in

 

ALR and AHR are alarm differentials referred to SP and SP+HYS.

SP

T[°]

SP+HYS+AHR

SP-ALR

ON

OFF

                

SP

T[°]

SP+AHR

SP-HYS-ALR

ON

OFF

           

ALA

-50... 120°

Low temperature alarm threshold.

AHA

-50... 120°

High temperature alarm threshold. 

ALR

-12... 0°

Low temperature alarm differential. With ALR=0 the low temperature alarm is excluded.

AHR

0... 12°

High temperature alarm differential. With AHR=0 the high temperature alarm is excluded.

ATI

T1; T2; T3

Probe used for temperature alarm detection.

ATD

0... 120min Delay before alarm temperature warning.

ADO

0... 30min

Delay before door open alarm warning.

AHM

NON;

ALR;

STP;

Operation in case of high condenser alarm

NON

 : high condenser alarm inhibited.

ALR

 : in case of alarm, “HC” flashes in the display and the buzzer is switched on.

STP 

: in addition to the alarm symbols displayed, the compressor is stopped  and defrosts are suspended.

AHT

-50...120°

Condensation temperature alarm (referred to T3 probe).

ACC

0...52

weeks

Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the 

ACC

 value programmed, 

“CL” flashes in the display. With ACC=0 the condenser cleaning warning is disabled and CND disappears from Info Menu.

IISM

NON;

MAN;

RTC;

HDD;

DI2

Switchover mode to second parameter set

NON

 : inhibition to use the second parameter group (

the following parameter will be 

SB

).

MAN

 : button   switches the two parameter groups over.

RTC

 : switchover to the second parameter group at STT time and back to the first group at EDT time

HDD

 : automatic switchover to the second parameter group, when heavy duty conditions are detected.

DI2

 : switchover to the second parameter group when the auxiliary DI2 input makes.

IISL

-50... IISH

Minimum limit for IISP

 

setting.

IISH

IISL... 120° Maximum limit for IISP

 

setting.

IISP

IISL... IISH Setpoint in mode 2.

IIHY

1... 10°

OFF/ON differential in mode 2.

IIFC

NON;TMP; 

TIM

Fan control in mode 2. See FCM.

HDS

1...5

Controller sensitivity for the automatic switchover from Group 

I

 to Group 

II

 (1=minimum, 5=maximum).

IIDF

0...99 hours Time interval among defrosts in mode 2.

SB

NO/YES

Stand-by button   enabling. 

DS

NO/YES

Door switch input enabling (closed when door is closed).

DI2

NON;

HPS;

IISM;

RDS;

DSY

DI2 digital input operation

NON

 : digital input 2 not active.

HPS

 : when contact opens a condensing unit high pressure alarm occurs.

IISM

 : when contact makes the controller will use group 2 parameters.

RDS

 : when contact makes a defrost is started (remote control).

DSY 

: defrost synchronisation. The controllers, linked as per Fig. 3, will all start and end defrost together. The first controller 

in defrost will get defrost of all the others started. The last controller ending defrost will get defrost of all the others stopped.

OFF

ON

COMPR.

ON

COMPR.

ON

COMPR. OFF

FT1

FT2

FT3

FT3

FT2

Fig.2 Time-optimised fan control (FCM=TIM)

Temperature alarm with relative thresholds,

refrigerating control (ATM=REL, C-H=REF).

Temperature alarm with relative thresholds,

heating control (ATM=REL, C-H=HEA).

Summary of Contents for TGU-2

Page 1: ...___________4 Installation of Leg Castors ________________5 Leveling Cabinet _________________________6 Electrical Instructions _____________________6 Start up _________________________________7 Shelvi...

Page 2: ...www truemfg com True Food International Equipment Inc...

Page 3: ...e to do so could be dangerous and may invalidate your warranty Unplug the refrigerator before cleaning and making repairs Setting temperature controls to 0 position does not isolate the unit from the...

Page 4: ...the unit is located there will be officially approved ways of disposing of your used equipment It is important that care is taken in disposing of used refrigerators or freezers Before You Throw Away Y...

Page 5: ...y issues and early failure of electrical components The use of adapters and extension cords will invalidate your warranty Always disconnect the unit by pulling on the plug and not on the power lead Do...

Page 6: ...lips Head Screwdriver Spirit Level REQUIRED TOOLS The following procedure is recommended for uncrating the unit A Remove the outer packaging by pulling tri wall nails from skid Remove 4 cardboard corn...

Page 7: ...imit to any single castor A Turn the bearing race counter clockwise until the cabinet is level Level front to back and side to side diagonally B Install the desired number of shims making sure the slo...

Page 8: ...NS LEVELING A Set unit in its final location Be sure there is adequate ventilation in your room Under extreme heat conditions 100 F 38 C you may want to install an exhaust fan WARNING Warranty is void...

Page 9: ...cal Be careful to load product so that it neither presses against the back wall nor comes within four inches of the evaporator housing Refrigerated air off the coil must circulate down the back wall N...

Page 10: ...rectangular hole of the standard posts Make sure tabs on the back side of the tray slide are facing down Push in and slide down on both ends so tabs are in the locked position See figure 1 Note Make s...

Page 11: ...od International Equipment Inc 9 9 IF YOUR CABINET IS BUILT WITH THIS TEMPERATURE CONTROL PLEASE SEE THE FOLLOWING INSTRUCTIONS For proper operation it is important to set correct time of day at time...

Page 12: ...www truemfg com True Food International Equipment Inc 10 10...

Page 13: ...C The compressor and evaporator fan s will cycle off 9 F 23 C and back on at 1 F 18 C D The LAE control may be preprogrammed to initiate defrost at specific times of day or intervals If additional De...

Page 14: ...fore door alarm AHM ALR operation for high cond alarm AHT 65 condensation temp alarm ACC 0 condenser period cleaning IISM NON switchover mode for 2nd parameter IISL 250 minimum limit for IISP setting...

Page 15: ...T MAY AFFECT CABINET OPERATION HOW A To change lock setting press and release the info button T1 will appear See image 1 Press and release the up button until Loc appears See image 2 B While pressing...

Page 16: ...info button press the up or down button to change the clock minutes See image 2 C Once the minutes have been set correctly release the info button and hrs will appear on the display See image 3 D Whi...

Page 17: ...t 30 seconds for the display to show temperature See image 4 and the stand by button at the same time press the up or down button to change press the up or down button to change Push the up button thr...

Page 18: ...and press again the manual defrost button for an additional 4 seconds HOW A To see the defrost times press and hold the info button and the stand by button at the same time ScL will appear See image 1...

Page 19: ...the value with button While keeping button pressed use button SETPOINT display and modification Press button for at least half second to display the setpoint value By keeping button pressed use butto...

Page 20: ...By keeping button pressed use button or to set the desired value When button is released the newly programmed value is stored and the following parameter is displayed To exit from the setup press butt...

Page 21: ...fferential With AHR 0 the high temperature alarm is excluded ATI T1 T2 T3 Probe used for temperature alarm detection ATD 0 120min Delay before alarm temperature warning ADO 0 30min Delay before door o...

Page 22: ...n Both compressors are turned off at the same time INP SN4 ST1 Temperature sensor selection With INP SN4 the probes must be the LAE models SN4 with INP ST1 the probes must be the LAE models ST1 OS1 12...

Page 23: ...ver Carefully slide compressor assembly back into position and replace bolts Step 8 Reinstall rear grill assembly onto unit Tighten all screws Step 9 Connect unit to power and check to see if compress...

Page 24: ...ong the polish lines Polishing lines or grain are visible on some stainless steels Always scrub parallel to visible lines on some stainless steels Use a plastic scouring pad or soft cloth when you can...

Reviews: