background image

2

Operating manual

TROX air terminal units

Type VFC volume flow controllers 

VFC

Area of application

TROX VFC series volume flow controllers are mechanical 

system-powered controllers for controlling the airflow in 

 

constant and variable air volume systems.

3 variants of the volume flow controllers are available:

• 

Constant volume flow rate

•   

min

- 

max

 switching

  

Actuator with potentiometers (type E01, E02)

 

Actuator with mechanical stops (type M01, M02)

• 

Variable volume flow rate, 

 

Actuator with potentiometers (type E03)

The set flow rate must always be set by the customer on site. 

The setting is made without adjustment devices. 

 

Each volume flow controller has a sticker with a characteristic 

for determining the volume flow rate. One or two settings 

 

are read off and transferred to the rotary knob or actuator 

(potentiometer or mechanical stops).

Operating modes

• 

Constant volume flow rate

 

The volume flow controller keeps the set flow rate constant 

independently of the duct pressure.

• 

Variable volume flow rate

 

The volume flow controller keeps a variable set flow rate 

constant independently of the duct pressure. For this  

purpose, the volume flow controller receives a control 

 

variable from a room temperature controller or air quality 

controller, a set point adjuster or a DDC outstation. The 

control variable is a 0 to 10 V DC voltage signal.

•   

min

- 

max

 switching

 

The volume flow controller works with two 

setpoint values 

that are switched over using switches or relays provided by 

the customer.

General information

Correct use

The volume flow controllers are suitable for use in ventilation 

 

and air conditioning systems. Particular conditions can 

restrict the functioning capacity and must be taken into 

account during the design stage:

• 

Use of VFC series volume flow controller in aircraft is not 

permitted.

• 

In systems with aggressive air, only air terminal units made 

of plastic should be used, subject to extensive tests for 

suitability.

•  Galvanised sheet steel units must not be installed in  

contaminated environments (e.g. acetic acid).

•  The controller and actuator do not contain any parts that 

can be exchanged or repaired by the user.

•  The actuator contains electronic components therefore 

must be separated from domestic waste. When disposed 

of, local up to date regulations must be complied with.

• 

The mechanical components of VFC series volume flow 

controllers are maintenance-free.

• 

Sticky constituents of the air, in particular in association 

with fluff, can lead to impairment or failure of the regulation 

function.

Safety notes

Danger!

Danger of electric shock! Do not touch any live 

components!  Electrical equipment carries a 

dangerous electrical voltage.

• 

Only skilled qualified electricians are allowed to 

work on the electrical system.

• 

Switch off the power supply before working on 

any electrical equipment. 

•  Safety transformers must be used.
•  Installation should only be carried out by specialists.  

The normal rules of site working, in particular the health 

and safety regulations must be complied with.

• 

For installation, wiring, and commissioning observe 

 

the recognised technical regulations, especially safety 

 

and accident prevention regulations.

• 

Due to the danger of injury on edges and burrs, transport 

and installation may only be performed while wearing 

gloves.

• 

Install the units proficiently with suspension points 

 

and secure with locknuts. Only load the suspension points 

with the units' own weight. Adjacent components and 

 

connecting ducts must be supported separately.

• 

Only use units with ATEX approval for rooms containing 

 

a potentially explosive atmosphere.

Summary of Contents for VFC series

Page 1: ...wiring____________________7 min max switching operation actuator with mechanical stops___________________________8 min max switching wiring______________________9 min max switching setting___________...

Page 2: ...must be taken into account during the design stage Use of VFC series volume flow controller in aircraft is not permitted In systems with aggressive air only air terminal units made of plastic should b...

Page 3: ...site using the rotary knob Factory setting 5 Actuator E01 E02 E03 For variable airflow rate or min max switching Volume flow rate is set on potentiometers Shut off down to leakage airflow is possible...

Page 4: ...and acoustic effects Horizontal or vertical installation in combination with volume flow rate measuring unit VMR arrange the sensor tubes at 45 offset from the controller axis Installation behind a be...

Page 5: ...7 8 9 10 3 4 5 6 7 8 9 10 80 6 7 10 14 19 25 33 42 20 26 35 49 68 91 119 150 100 6 10 15 22 30 40 50 65 22 36 54 79 108 144 180 234 125 11 15 22 30 44 60 78 100 40 54 79 108 160 215 280 360 160 18 31...

Page 6: ...manently on Position set Flashing once a second Actuator operating Flashing twice a second Actuator is jammed and stationary Off No supply voltage Actuator E03 The relationships between the setting va...

Page 7: ...A Switches provided by the customer volt free contacts can be used for making the switching procedures shown below 1 wire control illustration above Switch S1 open min Switch S1 closed max 2 wire cont...

Page 8: ...gnet is integrated in the removable position indicator Make the corresponding settings on the mechanical stops Deactivate gearbox disengagement again and reconnect the position indicator see also page...

Page 9: ...onnection data M01 24 V AC 20 50 60 Hz 1 VA 24 V DC 20 0 5 W M02 230 V AC 50 60 Hz 3 VA Switches provided by the customer volt free contacts can be used for making the switching procedures shown below...

Page 10: ...the reverse Place the magnet on the point indicated with magnetic gear release The gearbox is now disengaged and the actuator can be moved min max switching setting Remove the mechanical limiters Set...

Page 11: ...crew and move the rotary knob to position 5 The actuator is simply pushed on and it engages in the mounting bracket Order code for expansion sets see page 1 Fixing screw Setting 5 Mounting the actuato...

Page 12: ...ry to remove the locking screw and move the rotary knob to position 5 Order code for expansion sets see page 1 Locking screw Coupling Rotary knob 1 2 Perform the following steps to mount the actuator...

Reviews: