Smoke Detector

Type RM-O-VS

Approved by the German Institut für Bautechnik

4/6.1/EN/3

Summary of Contents for RM-O-VS

Page 1: ...Smoke Detector Type RM O VS Approved by the German Institut f r Bautechnik 4 6 1 EN 3...

Page 2: ...y condensation and water vapour can cause false alarms Warning limit for air flow 2 m s Warning limit for high pollution 70 10 units System monitoring electric fault EMC interference suppression to EN...

Page 3: ...by an LED and closing relay contact The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument Installation of a remote...

Page 4: ...r to replace the smoke alarm an inspection opening should be provided on the upper or lower side of the air duct Optional electrical connections mains connection and connection to control device of fi...

Page 5: ...trol device A on the fire damper to be controlled maximum switched power 250 V 10 A L1 Mains connection 230V 50 60 Hz L3 Control device connection volt free Switched power 250 V 10 A or 24 V 200 W L4...

Page 6: ...Velocity Monitoring Green LED System Monitoring Terminal Strip L9 6 5 Terminal Strip L9 4 3 Terminal Strip L9 2 1 Terminal Strip L3 2 3 1 Yellow LED Pollution Monitoring With air flow LED on Without a...

Page 7: ...rol devices on fire damper Response of smoke alarm to smoke aerosol e g cigarette smoke or smoke from smoke cartridge When the permitted concentration limit is exceeded the smoke alarm interrupts the...

Page 8: ...ution level on the smoke alarm sampling chamber and the system electronics maintenance once year Scope of supply see page 2 Order Example Make TROX Type RM O VS Quantity 5 RM O VS Order Code Descripti...