9
Technical data
General operating conditions of the control components
Ambient temperature
10–50 °C
Ambient humidity
5–90% rF
Easy controller LMV-D3AL-F
Supply voltage
24 V AC ± 20%, 50/60 Hz
Supply voltage
24 V DC -10/+20%
Power rating
3.5 VA max.
Power rating
Max. 2 W
Running time for 90°
120–150 s
Setpoint value signal input
0 – 10 V DC, Ra > 100 kΩ
Actual value signal output
0–10 V DC, max. 0.5 mA
IEC protection class
III (protective extra-low voltage)
Protection level
IP 20
EC conformity
EMC to 2014/30/EU
Easy controller 227V-024T-05-013
Supply voltage
24 V AC ± 20%, 50/60 Hz
Supply voltage
24 V DC ± 20%
Power rating
5 VA max.
Power rating
Max. 3 W
Running time for 90°
100 s
Setpoint value signal input
0 – 10 V DC, Ra > 100 kΩ
Actual value signal output
0 – 10 V DC, max. 0,5 mA
IEC protection class
III (protective extra-low voltage)
Protection level
IP 20
EC conformity
EMC to 2014/30/EU
Technical data
Control component Easy for VAV terminal units
31