BVD – installation manual for replacing the motor
Fig. 42: BVD
1.
Disconnect
2.
Disconnect the electric connecting cable (/20) from the terminal box (isolator if required, neither displayed).
3.
Remove the closing ring (/9).
4.
Remove the outside spacer ring (/8),
5.
Remove the eye nuts.
6.
Remove the rain hood (/10) (cut open the seal beforehand).
7.
7. Remove the mineral wool (/21), cover and cooling-air duct (/19).
8.
Remove the inside spacer ring (/15),
9.
Remove the inner ring (motor compartment).
10.
Remove the screws and mounting rods
11.
Disconnect the electric connecting cable (/20) from the terminal box of the motor.
12.
Remove the fixing plate (/3) with the motor (/1) and impeller (/2).
13.
Remove the crankshaft locking clip and pull off the impeller (/2).
14.
Remove the fixing plate (/3).
15.
Clean the crankshaft on the new motor (/1).
16.
Attach the fixing plate (/3) again.
17.
Fit the impeller /(2) and secure it again with the crankshaft locking clip.
Installation manuals
Centrifugal roof fans DRH; DRV; DRVF; DRVF-H; BVD; BVD(F600)
59
Summary of Contents for BVD F600
Page 47: ...Appendix Appendix Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 47...
Page 61: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 61...
Page 62: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 62...
Page 63: ...Centrifugal roof fans DRH DRV DRVF DRVF H BVD BVD F600 63...