Operating manual TROX TNC-EASYCONTROL
9
6
Commissioning
Terminals
Box and plug
Connection
1.
0V / GND
2.
Q0…5 / 24V
3.
I 0,2,4,6,8,10 / Closed
4.
I 1,3,5,7,9,11 / OPEN
Connection data
Cable diameter
max. 10.5 mm
at least 6.5 mm
Connection diameter
max. 2.5 mm²
min. 0.75 mm²
Connections per pole
1
Standard mode
②
4
①
4
4
4
4
4
4
③
LB1
LB2
LB3
LB4
LB5
LB6
Configuration with 6 fire dampers (standard operation = 1
fire damper per output)
① Type of cable, e.g. HMH 5 x 1.5 mm
2
(control cable with
better behaviour in the event of a fire, free of halogens)
② Duct smoke detector RM-O-D
③ Fire damper with factory mounted TNC-LINKBOX
Easy and quick connection of actuator cables to TNC-
EASYCONTROL is possible with the TNC-LINKBOX.
① ③
②
If you order the TNC-LINKBOX as an accessory, it will be
factory mounted. Together with a mounting plate it is factory
attached to the damper and wired to the actuator.
If mounting is to be carried out by others, the plugs of the
actuator can simply be connected to the sockets on the
TNC-LINKBOX.
Connect the 4 wires of the cable intended to connect the
TNC-LINKBOX and TNC-EASYCONTROL to the numbered
terminals in the BOX.