Trox Technik TNC-EASYCONTROL Operating And Installation Manual Download Page 13

6

 

Commissioning

 

Operating manual TROX TNC-EASYCONTROL

 

13

 

Terminal

 

Connection

 

1

 

0V / GND

2

 

24 V

3

 

I12 SD Smoke:

 

When  duct  smoke  detector  RM-O-3-D  or  RM- 

O-VS-D  or  the  central  fi re  alarm  system 

sends an alarm signal (NC contact), all fi re 

dampers

 

close, and an alarm is issued (output Q8). If you 
do not use this input, put a wire link between 
terminals 2 + 3.

 

Input and output signals

 

The inputs and outputs on the PCB of TNC-EASYCONTROL 

which are required for the communication with a higher-level 
system are already used by the preinstalled application 
software.

 

Outputs

 

The connection for the outputs is made with a GST15i5 

socket. All outputs are volt-free outputs.

 

The terminal connections are as follows:

 

Q    Q 

Inputs I0...I15

 

1    1    Q    Q    0 

4    2    9     8    V 

Inputs

 

Outputs Q0...Q15

 

Terminal 

Connection

 

0V / GND

 

Q8 Alarm1 Signal for smoke, fire; fire damper 
is closed

 

Q9 Alarm2 Signal for errors in the functional 
test; running time and end position error; 
smoke detector contamination

 

Q12 No fire damper is closed

 

The connection for the inputs is made with a GST15i3 plug. 

The terminal connections are as follows:

 

I      2

 

1     1     4

 

5     4     V

 

Q14 Functional test is active

 

Connecting a duct smoke detector

 

The connection for the inputs is made with a GST15i5 plug. 

The terminal connections are as follows:

 

I       I       2 

1     1     4     0 

3     2     V    V 

Terminal

 

Connection

 

1

 

24 V

2

 

I14 Start of functional test:

 

It is possible to start the functional test for all 

fire dampers with a signal from an external 
point (e.g. central BMS) and/or with a timer. 
The damper blades CLOSE and OPEN again. 
In case the running time is exceeded, the 
affected damper remains closed, and an alarm 
is generated (output Q9).

3

 

I15 External release

 

External signal (NC contact) to open all fire 
dampers. If you do not use this input, put a wire 
link between terminals 1 + 3.

FA input = 1 per TNC Easycontrol

Summary of Contents for TNC-EASYCONTROL

Page 1: ...Operating and installation manual TNC EASYCONTROL...

Page 2: ...damper actuator connection 8 6 Commissioning 9 Standard mode 9 Parallel operation 11 TNC LINKBOX as a distribution box 11 Input and output signals 13 GST connector assembly information 16 Operating st...

Page 3: ...y liability for any malfunction or damage resulting from non compliance with this manual or non compliance with relevant statutory regulations Other applicable documentation In addition to this instal...

Page 4: ...ally explosive atmospheres Residual risks Danger of electric shock Do not touch any live components Electrical equipment carries a dangerous electrical voltage Only skilled qualified electricians are...

Page 5: ...t using timer or external control by central BMS and manual triggering Output of alarm messages fire smoke fire damper closed fault during function test running limit switch faults smoke detector cont...

Page 6: ...ce point GND Display LED yellow Input voltage V 24 V DC nominal Input current mA typ 10 Activation level high V 15 30 DC Deactivation level low V 0 5 5 DC Outputs OUT 0 OUT 15 Number of outputs 16 2 8...

Page 7: ...ctive wrapping until just before installation Storage If you need to store the controller temporarily make sure that the following conditions apply Leave the unit in its packaging and do not expose it...

Page 8: ...m min 8 mm Connection diameter max 2 5 mm min 0 75 mm Connections per pole 1 Fire damper actuator connection TNC EASYCONTROL can be used to control and monitor up to six motorised fire dampers If two...

Page 9: ...able with better behaviour in the event of a fire free of halogens Duct smoke detector RM O D Fire damper with factory mounted TNC LINKBOX Easy and quick connection of actuator cables to TNC EASYCONTR...

Page 10: ...f you do not use the TNC LINKBOX for easy and quick wiring conventional wiring with a junction box is also possible In this case wiring should be as follows External wiring of a fire damper standard o...

Page 11: ...l operation up to 12 fire dampers It is possible to use the TNC LINKBOX also for the parallel operation of two motorised fire dampers In this case the TNC LINKBOX acts as a distribution box This confi...

Page 12: ...GND 2 Q0 5 24V 3 I 0 2 4 6 8 10 Closed 4 I 1 3 5 7 9 11 OPEN Connection data max 10 5 mm Cable diameter Connection diameter at least 6 5 mm max 2 5 mm min 0 75 mm Connections per pole 1 If you do not...

Page 13: ...smoke fire fire damper is closed 3 Q9 Alarm2 Signal for errors in the functional test running time and end position error smoke detector contamination 4 Q12 No fire damper is closed The connection for...

Page 14: ...VS D sends a contamination signal NO contact an alarm is generated output Q9 This alarm is a warning and is generated when the contamination level is 70 All re dampers remain open Connecting display T...

Page 15: ...for FD6 ncc I11 Fire damper6 OPEN Limit switch for FD6 noc I12 SD 1 Smoke SD switch ncc I13 SD 1 Contamination SD switch noc I14 Start of functional test Functional test noc I15 External release Relea...

Page 16: ...Ith one exception Black and white connectors have the same coding According to the local regulations for health and safety at work and general safety regulations lockable plugs have to be used GST dis...

Page 17: ...tched off and output Q9 Alarm 2 is switched off Functional test monitoring of the running time The functional test for the fire dampers is started on input I14 positive edge either by pressing a butto...

Page 18: ...nu using EXIt requires that all fire dampers are OPEN Use buttons S3 and S4 in the menu to select an item Activate the function with S5 IMPORTANT In case of a 4 wire connection 24 V DC are supplied to...

Page 19: ...amper OPEN yellow fire damper actuator is running red fire damper CLOSED error Function bar LED green Display OK red error Function buttons Cursor up down left right Function buttons The symbols in th...

Page 20: ...n left right IP protection level IP 67 when installed in the front panel of the casing otherwise IP 65 Operating temperature C 20 70 Supply voltage V 8 32 DC Current consumption mA 70 at 24VDC CAN int...

Page 21: ...the control The connected fire dampers open Duration about 170 s displayed in yellow System OK The connected fire dampers are open displayed in green Menu change with with F button below Enter the pa...

Page 22: ...TNC EASYCONTROL Manual control of the fire damper Manual mode preselection using the function button below Manual control Select fire damper with Open fire damper with Close fire damper with Menu cha...

Page 23: ...the functional button below Menu change with Start test with the functional button below Counter reset set test cycle counter to 0 using the function button below Test is active Duration about 170 s d...

Page 24: ...the function button below System error Duct smoke detector is contaminated Fire damper running time error or limit switch error affected fire damper is displayed in red Check rotary switch S2 Acknowle...

Page 25: ...to damage to property additional safety measures must be installed to prevent this Cleaning Use only mild non scouring cleaning agents Never use aggressive cleaners such as solvents or benzine Mainten...

Page 26: ...and 4 FD2 are the inputs for the position signals Note Counting is from the right to the left 24 V DC must be supplied to the inputs of TNC EASYCONTROL hence the limit switches must also be supplied w...

Page 27: ...to C Select the language German or English using the function button below Fire alarm The contact has been interrupted thermal release of the fire damper Acknowledgement reset with the function button...

Page 28: ...X TNC EASYCONTROL 6 Inbetriebnahme TROX GmbH Heinrich Trox Platz D 47504Neukirchen Vluyn Telefon 49 0 28 45 2 02 0 Telefax 49 0 28 45 2 02 2 65 E Mail trox trox de www trox de Subject to change All ri...

Reviews: