Product description and dimensions
Application
• Control system encased in sheet steel casing with cutout
window, including power supply unit and timer, completely
wired and ready for plug-in
• Control of up to 6 motorised fire dampers with 24 V DC (up
to 12 fire dampers with parallel operation); alternatively for
capturing the end positions of up to 12 mechanical dampers
with one limit switch (up to 24 limit switches with parallel
operation)
• With pre-installed user software, ready to use
• Topology: star-shaped with 4-wire line
• Manual control (OPEN/CLOSE) of individual fire dampers
• Monitoring of the fire damper opening and closure times
• Automated and time-controlled function test using timer,
or external control by central BMS and manual triggering
• Output of alarm messages: fire, smoke, fire damper closed,
fault during function test, running/limit switch faults, smoke
detector contamination
• Menu-driven operation using integral LCD and softkeys on
the main PCB, signalling with LEDs
Accessories
• Z01
– LED/buzzer combination for alarm signalling
– Mounted into the cover plate and completely wired (ready
to use)
• Z02
– 2.8 inch colour LCD, mounted into the cover plate and
completely wired (ready to use)
– For displaying damper blade positions
– For controlling individual fire dampers
– For starting a functional test
• Z03
– 2.8 inch colour LCD and LED/buzzer combination
When a TP043EC display is used for operation and as a
communication master, two TNC-EASYCONTROL units may
be used in combination.
Maintenance
• Maintenance-free as construction and materials are not
subject to wear
TNC-EASYCONTROL Z01 - Z03
400
110
TNC-EASYCONTROL, version Z00
400
85