Fixing to the ceiling slab

Personnel:

HVAC technician

Protective equipment:

Industrial safety helmet

Protective gloves

Safety shoes

If possible, install the device before fixing the ceiling
tiles; if this is not possible, remove the adjacent
ceiling tiles.

The TFM can weigh up to 35 kg, depending on the
construction. Use only approved and adequately
sized suspension systems. Fixing material is not
included in the supply package.

Only work in pairs; preferably use a lift.

 DANGER!

Danger of death from the fall of suspended
loads!

Only use fixing materials designed for the
required load.

Use all hanging brackets supplied.

Stand clear of suspended loads, unless
properly secured.

Check secure fixing after installation.

1.

Remove the clamping frame from the
casing. To do so, loosen the clamping
screws (Fig. 1/5), then remove the clamping
frame (Fig. 1/4). Remove and dispose of the
spacers; keep the clamping frame as you
will need it again later.

Fig. 2: Fixing

Suspension lug with drilled hole 

 12 mm

Threaded rod

Lock nut

Nut

2.

Fix any suspension elements, e.g. threaded
rods (Fig. 2/2), to the ceiling.

3.

Start by suspending the TFM casing on
three suspension lugs (Fig. 2/1); ensure that
the casing is horizontal, fix the nuts accord-
ingly (Fig. 2/4), then use the locknuts
(Fig. 2/3) to secure the suspended casing.

Loads imposed on the casing may impair
the function of the unit. Be sure to install the
unit without torsion.

4.

Fix the fourth threaded rod without changing
the position of the TFM casing and secure it
with a locknut.

Assembly

 

TFM Particulate filter modules for ceilings

5

Summary of Contents for TFM

Page 1: ...nt Clamping screw Diffuser face Screw fixing diffuser face Sealing plug for connecting holes Installation and maintenance manual GB en TFM Particulate filter modules for ceilings TROX GmbH Heinrich Tr...

Page 2: ...erence to the applicable standards and guidelines the state of the art and our expertise and experience of many years The manufacturer does not accept any liability for damages resulting from Non comp...

Page 3: ...ular checks and smaller adjustments Personal protective equipment Personal protective equipment must be worn for any work in order to reduce health or safety haz ards to the minimum The appropriate pr...

Page 4: ...unit from the effects of weather Protect the unit from humidity dust and con tamination Storage temperature 10 C to 50 C Relative humidity 95 max no condensation Assembly General information Fix the...

Page 5: ...secure fixing after installation 1 Remove the clamping frame from the casing To do so loosen the clamping screws Fig 1 5 then remove the clamping frame Fig 1 4 Remove and dispose of the spacers keep...

Page 6: ...stem as long as the modules were connected with one another correctly However the increased load on the suspension system must be taken into account 1 Remove the sealing plug on the connecting sides o...

Page 7: ...d air conditioning system for 24 hours before you insert the filter element Volume flow rate balancing To adjust the ventilation and air conditioning system you first have to carry out volume flow rat...

Page 8: ...ave inserted the filter element check that there are no leaks Leakage test on an installed filter on page 9 6 Installing the diffuser face Installing the diffuser face Fig 6 TFM assembly diffuser face...

Page 9: ...sealing integrity testing leakage testing filter changes or cleaning require you to remove the diffuser face Fig 7 Removing the diffuser face Unscrew the knurled screws Fig 7 2 and remove diffuser fa...

Page 10: ...er frame There are two ways to measure the differential pressure Permanent measurement Continuous differential pressure measurement and monitoring of the final differential pressure This is done with...

Page 11: ...page 7 Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacte...

Page 12: ...ation It is then sufficient to clean and disinfect wipe the filter casing and the diffuser face this has to be done for the first time just before the ventilation and air conditioning system is switch...