Sealing integrity test

Fig. 9: Sealing integrity test

The casing is fitted with a sealing integrity test
facility. Sealing integrity is tested with a sealing
integrity test device (see operating manual).

1.

Connect the sealing integrity test device
(Fig. 9/3) to the connection point on the filter
(Fig. 9/2).

2.

Apply at least 2000 Pa to the test groove
(Fig. 9/1).

3.

Check the leakage rate on the flow rate
meter of the sealing integrity test device.

ð

The value must not exceed 0.003% of
the nominal volume flow rate.

If this value is exceeded, adjust the clamping
screws or the clamping frame; also check the seal,
test groove and filter element for damage. Then
repeat the sealing integrity test.

Differential pressure measurement

The initial differential pressure for TROX filters is
given on the label on the filter frame.

There are two ways to measure the differential
pressure:

Permanent measurement:

 Continuous differential

pressure measurement and monitoring of the final
differential pressure. This is done with a static differ-
ential pressure measuring device (Fig. 10/1), e.g.
TROX MD-UT, MD-APC or MD-DPC, using the
pressure measurement points (Fig. 10/2) at the side
or on the top of the casing.

Fig. 10: TROX MD-DPC connection

Connecting a stationary measuring device

Plus (+)

- to the 'Plus' measurement point (+)

Minus (–) - to the 'Minus' measurement point (–)

Temporary measurement: 

Temporary differential

pressure measurement with a mobile measurement
device connected to the internal measuring tube
(Fig. 10). For this, you have to remove the diffuser
face, 

Ä

  9

.

Connecting a mobile measuring device

Plus (+)

- to the internal measuring tube

(Fig. 8/1)

Minus (–) - Don't connect; the differential pressure

is measured against the room pres-
sure.

Re-attach the plugs (Fig. 10/3) after the measure-
ment.

Maintenance

 

TFM Particulate filter modules for ceilings

10

Summary of Contents for TFM

Page 1: ...nt Clamping screw Diffuser face Screw fixing diffuser face Sealing plug for connecting holes Installation and maintenance manual GB en TFM Particulate filter modules for ceilings TROX GmbH Heinrich Tr...

Page 2: ...erence to the applicable standards and guidelines the state of the art and our expertise and experience of many years The manufacturer does not accept any liability for damages resulting from Non comp...

Page 3: ...ular checks and smaller adjustments Personal protective equipment Personal protective equipment must be worn for any work in order to reduce health or safety haz ards to the minimum The appropriate pr...

Page 4: ...unit from the effects of weather Protect the unit from humidity dust and con tamination Storage temperature 10 C to 50 C Relative humidity 95 max no condensation Assembly General information Fix the...

Page 5: ...secure fixing after installation 1 Remove the clamping frame from the casing To do so loosen the clamping screws Fig 1 5 then remove the clamping frame Fig 1 4 Remove and dispose of the spacers keep...

Page 6: ...stem as long as the modules were connected with one another correctly However the increased load on the suspension system must be taken into account 1 Remove the sealing plug on the connecting sides o...

Page 7: ...d air conditioning system for 24 hours before you insert the filter element Volume flow rate balancing To adjust the ventilation and air conditioning system you first have to carry out volume flow rat...

Page 8: ...ave inserted the filter element check that there are no leaks Leakage test on an installed filter on page 9 6 Installing the diffuser face Installing the diffuser face Fig 6 TFM assembly diffuser face...

Page 9: ...sealing integrity testing leakage testing filter changes or cleaning require you to remove the diffuser face Fig 7 Removing the diffuser face Unscrew the knurled screws Fig 7 2 and remove diffuser fa...

Page 10: ...er frame There are two ways to measure the differential pressure Permanent measurement Continuous differential pressure measurement and monitoring of the final differential pressure This is done with...

Page 11: ...page 7 Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacte...

Page 12: ...ation It is then sufficient to clean and disinfect wipe the filter casing and the diffuser face this has to be done for the first time just before the ventilation and air conditioning system is switch...

Reviews: